NYC Law Department release
Independent mirror · updated as the City releases more · v1.3.2
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

Indoor Air Quality Report, P.S. 150M, Apr 2002

Machine-extracted title · confidence 97%

Letter reporting indoor air quality measurements conducted at P.S. 150M to evaluate conditions prior to re-occupancy.

NYC-WTC_000177934–000177937
Page image
Scanned page image, NYC-WTC_000177936
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan April 11,2002 Indoor Air Quality Assessment Page 3 P. S. 150M ATC Project No. 15-19125-0289

Real-Time Environmental Measurements

ATC collected forty (40) sets of real-time environmental measurements consisting of thirty (30) from inside the school building and ten (10) from outdoors. All three floors of the school building were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 2:10 P.M. and concluded at approximately 3:00 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 70.1 °F to 72.4 °F. All of the measurements were within the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 68.6 °F to 69.2 °F.

Relative Humidity

The relative humidity indoors ranged from 32.1 to 34.9 percent. All of the measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 23.2 to 33.9 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 401 ppm to 1001 ppm. All of the CO2 measurements were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 672 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1372 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide indoor concentrations were I ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 1 ppm for all collected readings.

Respirable Particulates (PM2,5) ppm.

Respirable particulate concentrations* indoors ranged between 1 pg/m^ to 26 pg/m^, None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration for the entire school building was approximately 20 pg/m^. The PM2,5 average concentration was below the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration measurements ranged from 17 to 24 pg/m^ with an average of 21 pg/m^. None of the outdoor measurements were

CONFIDENTIAL, CITY_21MC100_005759535 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000177936

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000177936Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000177954

Letter reporting indoor air quality measurements conducted at P.S. 150M to evaluate conditions prior to re-occupancy.

Similar indexed content

NYC-WTC_000177946

Letter reporting indoor air quality measurements conducted at P.S. 150M to evaluate conditions prior to re-occupancy.

Similar indexed content

NYC-WTC_000177942

Letter reporting indoor air quality measurements conducted at P.S. 150M to evaluate conditions prior to re-occupancy.

Similar indexed content

Compare copies and versions →