NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan April 11,2002
Indoor Air Quality Assessment Page 3
P. S. 150M ATC Project No. 15-19125-0289
Real-Time Environmental Measurements
ATC collected forty (40) sets of real-time environmental measurements consisting of thirty (30)
from inside the school building and ten (10) from outdoors. All three floors of the school
building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 2:10 P.M. and concluded at
approximately 3:00 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 70.1 °F to 72.4 °F. All of the
measurements were within the range of 68 to 75°F (at 50 percent relative humidity) as
recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime
conditions). The outdoor temperature measurements ranged from 68.6 °F to 69.2 °F.
Relative Humidity
The relative humidity indoors ranged from 32.1 to 34.9 percent. All of the measurements were
within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor
relative humidity measurements ranged from 23.2 to 33.9 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 401 ppm to 1001 ppm. All of the CO2
measurements were within the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The maximum outdoor (background)
CO2 concentration was 672 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1372 ppm (background level + 700 ppm). Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator
of available outside makeup air. The primary source of CO2 indoors is occupant respiration.
The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide indoor concentrations were I ppm for all readings. These concentrations were
below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 1 ppm
for all collected readings.
Respirable Particulates (PM2,5) ppm.
Respirable particulate concentrations* indoors ranged between 1 pg/m^ to 26 pg/m^, None of
the indoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration
of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5
concentration for the entire school building was approximately 20 pg/m^. The PM2,5 average
concentration was below the USEPA recommended concentration of 40 pg/m^ for sensitive
individuals and children. The outdoor respirable particulate concentration measurements ranged
from 17 to 24 pg/m^ with an average of 21 pg/m^. None of the outdoor measurements were
CONFIDENTIAL, CITY_21MC100_005759535
SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000177936
OCR can misread numbers and units. Confirm readings against the page image before using them.