Mr. Bernard P. Orlan August 28, 2002 Indoor Air Quality Assessment Page 3 'P.S. 130 M_____________________________ ArCProiectNpJ5-19125-0345 Real-Time Environmental Measurements

ATC collected fifty (50) sets of real-time environmental measurements consisting of forty-eight (48) in the school building and two (2) outdoors. All floors of the school were surveyed. Field data sheets are found in the Attachment. Readings were collected in the morning and evening. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 74 to 84,4 ®F. Thirty-nine (39) of the indoor measurements were above the range of 73 to79 °F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature ranged from 78.8 to 79,2 °F.

Relative Humidity

The relative humidity indoors ranged from 40.5 percent to 52 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 44.5 to J 48.2 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 456 ppm to 1270 ppm. One (1) of the indoor measurement for CO? was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO? concentration was 430 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1130 ppm (background level -1- 700 ppm). The highest reading was measured in room 304 with 21 occupants at 9:55 AM. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Qn^bon^fono^e Concentration

Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. These concentrations were within the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations was 2 ppm for all readings

Respirable Particulates (PM}^)

Respirable particulate concentrations* indoors ranged between 19 pg/m^ to 45 pg/m3 with an average 32 pg/m^' None of the indoor measurements for PM2,5 were above the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Eight (8) of the forty-eight (48) instantaneous indoor readings were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 24 pg/m3 to 26 pg/m3 with an average of 25 pg/m3. All of the outdoor measurements for PM2.5 were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2,5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m3 for sensitive individuals such as asthmatic people and children.

CONFIDENTIAL, CITY_2IMCl00_003430412 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000175152

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000175152Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000180183

Cover letter from ATC Associates to the NYC Board of Education submitting indoor air quality measurements for 90 Trinity Place in March 2002.

Similar indexed content

NYC-WTC_000179985

Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 21, 2002.

Similar indexed content

Compare copies and versions →