Lighting criteria specifications for audiovisual rooms, Jan 1999

Machine-extracted title · confidence 50%

Technical excerpt outlining lighting criteria and fixture zoning requirements for audiovisual rooms in the Mayor's Office.

NYC-WTC_000174020–000174021

Folder label: “Lighting Criterial for Audiovisual Rooms®Architect's Summary of Audiovisual BaseBuilding Requirements

Page image
Scanned page image, NYC-WTC_000174020
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

SWANKE HAYDEN CONNELL 1^003 01/07/99 12:32 FAX 21221902.'>6 11002 01/07/99 THU 08.38 FAX 212 725 0864 SHEN MILSOM & WILKE

XII. LIGHTING CRITERIA FOR AUDIOVISUAL ROOMS

Fixtures should be zoned and controllable in order to provide appropriate lighting scenes for typical conference, presentation and projection modes, as well as video teleconference applications, where applicable.

Zoned, dimmable, incandescent downlighting provides die most flexibility for general usage, presentation and projection applications. The front row(s) of fixtures must be on an independent zone. This way, in projection mode, the lights nearest the jirojection screens can be turned off independently while having the remaining zones provide low level illumination of the audience to facilitate note taking, etc.

Lighting for video conference/distance learning applications is very critical due to requirements of the cameras. Fluorescent bulbs with a color temperature of 35(X)“K Eire recommended since they yield a natural lighting with minimal coloration effects to flesh tones. Directional lenses combined with proper zoning will provide a high illumination level of the conference participants while maintaining lower light levels and reduced glare at the front (monitor/screen) wall. Fluorescent lighting is also used with consideration of HVAC requirements since incandescent has greater demands.

The Ml/nvinp illumination levels are rei ended

Dedicated Video Conference Rooms: l'able: 80fc at the face (vertical) f'ront (monitor) wall: less than 40fc Rear & side walls: 45 - 6Ofc

Multi-Purpose Rooms - Video Conferencing on a portable or limited basis: Evenly distributed illumination at a minimum level of 80fc will typically yield satisfactory results, however, improvements towards above criteria for dedicated rooms

MAYOR’S OFFICE OF EMERGENCY MANAGEMENT SMW#5149 Architect'is Summary of Audiovisual Basebuilding Requirements January 13,1998 Page- 13 -

NYC-WTC_000174020

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000174020Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

23rd floor punch list, 7 WTC, June 1999 · Box 7DCAS

NYC-WTC_000173500

Comprehensive punch list compiled by the Mayor's Office of Emergency Management following site inspections of the 23rd floor at 7 World Trade Center.

1 shared non-person entities · 1 shared topics · Same agency, volume and box · similarity 0.831

machine-extracted · confidence unavailable · Check page ↗

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →