UPS FOR AUDIO VISUAL
OEM
FEBRUARY 16, 1999
Add 50 KV.A UPS system with 20 minute battery supply. An $' x 9' room with conditioned air
will be required tm house this equipment. A feeder from the UPS to the panel presently provided
for the AV equipment will be required. Wire UPS to all AV equipment. Provide a 2 ton water
cooled DX unit supplied by emergency power. Exact location of UPS and A/C unit has not yet
been determined.