Project NO.5576A Total RFI's Received 34
Revised 09/03/98 Total Responses Received 29
RFI LOG
RFI ; DATE SUBJECT/DIVISION/DWG NO. RESPONSE DATE # BUS Remarks
NO. REC'D 'V RESR. DAYS
22 8/18/98 THE SMOKE DETECTOR THAT IS LOCATED UNDER THE LOW PROFILE DETECTORS LESS THAN 2" ARE AVAILABLE. 9/3/98 MEMO FROM
RAISED FLOOR IS BIGGER IN SIZE THAN THE 4" FOR THE USE LOW PROFILE DETECTORS AND SHALOW BACK BOX. COSENTINI. Sibam
FLOOR. WHERE SHOULD WE LOCATE THIS DETECTORS? Gounder.
(PIU ROOM CONFLICT ONLY)
23 9/2/98 PLEASE ADVISE ON PENDANT LENTH, TYPES C8,C12 AND 0
24 9/298 TYPE " N " FIXTURE , CABLE OR STEM MOUNTED? PLEASE
ADVISE ON LENTH.
25 9/2/98 COLOR OF LAMPS PER FIXTURE TYPE
26 9/298 COLOR CHIP FOR TYPE "N" AND TYPE"O" ?
27 9/2/98 PLEASE ADVISE ON REASON OF RESUBMISSION FOR
TYPES "P" AND TYPE "P-EM".
28 9/3/98 PLENUMS TO LINEAR DIFFUSERS, ARE THEY LINED? LINING IS REQUIRED IF PLENUM IS LOCATED LESS THAN 9/3/98 MEMO FROM
15 FEET FROM THE AIR TERMINAL. OTHERWISE COSENTINI Vai
INSULATION ONLY. Lemeshrv.