OEM Swanke Hayden Connell Architects
7 World Trade Center
Project NO.5576A Total RFI's Received 28
Revised 08/25/98 Total Responses Received 28
RFI LOG
RFI ©AYES ; SUBJECT/DIVISION/DWG NO. RESPONSE ItiAte /iTBUS! Remarks
NO. /REG© ■'/’Y J RESP. DAYS
1 7/17/98 RETURN AIR DUCT ABOBE THE TYPE # 3 WALL BETWEEN FSK-1 WAS ISSUED ON 7/22/98 FOR PRICING OF OFFSET 7/22/98 4 FIELD CONDITION.
EOC AND CORR. INTERFERESC WITH FULL HT. (SLAB TO 3PLY WALL. AMBASSADOR TO PRICE MOVING AND/ OR
SLAB) PARTITION. PRVIDING NEW DUCT TO CLEAR WALL.
2 7/17/98 IN CORR. ADJACENT TO ROOM 23-43 THERE ARE (2) WET COLUMNS WILL BE FURRED OUTAS PER REVISED 7/22/98 2
COLUMNS WITH RISER PIPING ENCROCHING DRAWINGS, ISSUED FOR BULLETIN # 1 DATED 07/24/98 (
APPROXIMATELY 13" INTO CORR. VERBAL FIELD INSTRUCTIONS WHERE ISSUED 07/21/98)
'3 7/17/98 IF DOOR 7A IS tO BE'b'la'ST PROOF. THE MANUFACTURER' THE DOOR IS HM, BUT THE SPECS CALL FOR LAMINATION 7/21/98 2
ADVICES THAT THEY CAN NOT PROVIDE WITH EMI OF VENEER THE SHIELDING COULD BE LAMINATED TO THE
SHIELDING. DOOR AND THEN COVERED WITH THE VENEER.
'4' '7/17/98 'hurricane WALL CONTRACTOR WOULD LIKE SHCA TO SHCA WILL ACCEPT PANEL SYSTEM AS LONG AS 7/21/98 2 CANTOR HAS
CONSIDER ALT. PREFAB. PANEL SYSTEM. CONTRACTOR PROVIDES SHOP DRAWINGSAND ACCEPTED
STRUCTURAL CALCULATIONS THAT PROVE IS EQUAL TO DRETAILS FOR
DESIGN. STEEL PLATE
5 7/17/98 DOES CONC. CURB AT 7TH. FLOOR AND 23RD. FLOOR HAVE AS PER CONVERSATION WITH STRUCTURAL ENGINEER .IT 7/20/98 3
TO BE CHOPPED INTO THE SLAB. CAN WE ACCOMPLISH IS NOT ACCEPTABLE TO SHOOT RODS OR ANCHORS TO
THE SAME THING BY DRIVING OR SHOOTING IN ANCHORS. SLAB.
6 7/31/98 DUCT INTEFERENCE WITH WALL BETWEEN CORRIDOR AND BUILD (2) LAYER WALL TO UNDERSIDE OF DUCT AND ADD 8/4/98 4
LIBRARY SOUND INSULATION ABOVE CEILING TILES A MINIMUM OF
2-0" FROM WALL ON BOTH SIDES OF CORRIDOR.
7 7/31/98 DUCT INTEFERENCE WITH WALL BETWEEN CORRIDOR AND' 'build®'LAYER WALL TO UNDERSIDEOF DUCT AND ADD' 8/4/98 4
TRAINING ROOM. SOUND INSULATION ABOVE CEILING TILES A MINIMUM OF
2-0" FROM WALL ON BOTH SIDES OF CORRIDOR.
8 7/31/98 HEIGHT OF OUTLET SHOWN ON DWG. A-23-3 AND A-23-4 LOCATE OUTLETS AS PER DRAWING A-23-4 18" A.F.F. 8/4/98 4
DIFFER
9 7/31/98 OVERLY REQUESTED INFORMATION ON UL LABELS. ( DO NO THIS ARE NOT RATED DOORS. 8/4/98
LBR DOORS HAVE TO HAVE UL LAVELS.)