23rd Floor “Shell” Condition

a. Air-Conditioning: 2-45 ton Trane units. The MER has an invertor controlling fan speed. Condenser water is supplied by 5-125 H P. pumps; 3,040 G.P.M. SUMMER; Not more than 76 degrees F dry bulb/INSIDE, when OUTSIDE temperatures reach a high, up to 95 degrees F dry bulb, 74 wet bulb with 5 watts for light and power per rentable square foot and 1 person per 100 rentable square feet. WINTER: Not less than 72 degrees F dry bulb/INSIDE when OUTSIDE temperatures reach a low, up to -10 degrees F dry bulb.

b. Sprinkler system; The sprinkler system is located in the B closet and is provided for all floors. the system is fed from the 6” standpipe riser. Distribution is the responsibility of the tenant. The standpipe system is supplied by 3 risers located in stairway A & B and at column #79 on the North East side of the building. Hoses and racks are provided in these areas. The sprinkler and standpipe systems are supplied by 2 house tanks, 27,000 gallons each with a fire reserve of 7,500 gallons each. Siamese connections.

c. Electrical Power: The building is provided with 4 feeders from the Con Edison sub station. Electrical power is distributed to the floor by 3 bus ducts. 2 of the electrical closets (there are 4) on the floor contain transformers for stepping down the power from 460 volts to 277 and 208/120 volts. Each electrical closet has a distribution panel rated for 70 amps.

d. Windows: The floor has approximately 150 Solar Bronze windows. Window coverings are the responsibility of the tenant.

e. Life Safety systems: The building endeavors to comply with all applicable codes as they apply to its life safety systems.

f. Spray on Fireproofing: Structural steel members are fireproofed in accordance with applicable code. g. Public Corridor Demising Partition; Not required if The City occupies the entire 23rd floor as proposed.

h. Slab Leveling: Not required, 7 World Trade Center is a new building.

7

NYC-WTC_000168244

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000168244Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000173475 · Box 7DCAS

Letter providing comments on submitted architectural plans for the Mayor's Office of Emergency Management.

Similar indexed content

Compare copies and versions →