NYC Law Department release
Independent mirror · updated as the City releases more · v1.2.6
← Document results/DEP Box 44/P.A WTC C-81, DEY St. Replacement Sewer (WTC-DEY ST UNDERPASS)
Document / 2 pages

DEP Plan Review Comments, WTC Underpass Sewer, May 1980

Machine-extracted title · confidence 95%

Letter from DEP to Port Authority requesting updated plans and specifying concrete encasement for a proposed ductile iron pipe under Church Street.

NYC-WTC_000165597–000165598

Folder label: “P.A WTC C-81, DEY St. Replacement Sewer (WTC-DEY ST UNDERPASS)

Page image
Scanned page image, NYC-WTC_000165597
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

231.020

May 13, 1980

Mr. R. M. Monti, P.E. RE: WTC-776.00; Dey Street Chief Engineer Underpass & Utility Port Authority of N.Y. & N.J. Relocation One World Trade Center New York, New York 10048 Borough of Manhattan

Gentlemen:

In reply to your revised submittal of Drawing No. 3 of the plans for the referenced project, with your letter dated April 2, 1980, please be advised that no approval can be given for these plans until the following comments are complied with:

1) Two (2) complete sets of the latest plans should be submitted for our review showing all up-dated revisions, so that new information shown on Drawing 3 can be examined in profile, section or detail as shown on other sheets.

2) The plans should indicate the distinction between those existing utilities to remain and these to be removed or abandoned, especially where they are close to existing or proposed sewers.

3) The proposed 15” dia. ductile iron pipe between new sewer man­ hole 3 and the existing M,H. in Church Street should be completely encased in concrete, since it will be located beneath other utilities. In addition, the clearances between this pipe and the escalator structure, as well as all the utilities crossing it should be shown in a revised profile drawing. This was not done in the previous profile drawing.

4) Revised plans should include a profile along the existing 3’-6” X 2'-8” sewer in Church Street, showing clearances with the escalator structure and with all other proposed and existing utility lines .-to remain.

NYC-WTC_000165597

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000165597Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

DEP letter re WTC river intake plans, May 1982 · Box DEP Box 44

NYC-WTC_000165078

Department of Environmental Protection letter dated May 28, 1982, providing comments on submitted plans for relocating river water intake lines at the World Trade Center.

1 shared non-person entities · 1 shared topics · Same agency, volume and box · similarity 0.946

machine-extracted · confidence unavailable · Check page ↗

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →