c. Control Cables'
(1) Splices shall be according to the manu
facturer’s recommendation.
(2) Terminations shall be indenter type
ring tongue terminals.
I
10. Splices in 600 volt multi-conductor rubber or
plastic-insulated, control, signal or communica
tion Ccibles 'With non-metallic covering, shall be
made in accordance with the Port Authority Stan
dard Drawings. Wl>ere the Contract Drawing re
quires splices for which there is no standard
Drawing, tl»e splices shall be similar in make-up
to the most applicable splice for which there is
a standard Drawing, The Contractor shall submit
Shop Drawings of all splices for which there are
no standard Drawings for approval.
11. Cable Splicing and Terminating Materials
a. All materials required for making splices or
terminations on specified wire or cable
siiall be supplied in complete kits by indi
vidual cable manufacturer or by one of the
following companies:
(1) Plymouth Rubber Co. - Canton, Mass.
(2) Cables Associates, Inc. - Long Island
City, N.Y.
(3) Amerace-Esna Corp. Elastimold Division,
Esna Park, Hackettstown, N.Y,
(4) Max Products Inc., - Kearny, N.J.
(5) 02 Electrical Mfg. Co., Brooklyn,
N.Y.
(6) PLM Products - Cleveland, Ohio.
Electrical Work
16020-12