December 17, 2002 114 LIBERTY STREET REMOVAL OF DUST, DEBRIS, AND CONTAMINATED MATERIALS
"RAM AIR 2M" as manufactured by Aramsco of Thorofare, NJ, or "Environmental Ltd., 300" as manufactured by Torchcross Agency Environmental, Hagerstown, MD or approved equal.
PART 3- EXECUTION
3.01 PRESSURE DIFFERENTIAL ISOLATION:
A. The Contractor shall coordinate this item with the Building Owner at the commencement of work.
B. In all areas, an alternate ventilation system must be installed. Portable Air Filtration Devices, capable of moving large quantities of air through a HEPA (High Efficiency Particulate Air filter capable of 99.97% efficiency at 0.3 microns) are to be installed. Each unit shall be serviced by a dedicated minimum 115V-20A circuit with ground fault circuit interrupter(GFCI)supplied from temporary power supply installed under requirements of Section 06, Temporary Facilities. Do not use existing branch circuits to power fan units.
C. Provide brand new AFDs, or provide on-site certificate of the HEPA filters. Certify that the AFDs have been tested via the DOP smoke challenge procedure and shall conform to GSA's Federal Standard 209B; ANSI N101.1; and MIL-F 51068E, as published by the US Army.
D. The Contractor shall size each zone area, provide the number of AFDs to guarantee no less than four (4) complete air changes per hour during contaminated dust and debris removal and clean-up.
1. Portable AFD use and positioning shall conform to ANSI Z9.2 and is to be coordinated with Ambient Group, Inc.
2. The Contractor shall provide a minimum of one (1) additional AFD unit for each Work Area as a back-up.
E. Locate fan unit(s) so that makeup air enters the Work Area primarily through decontamination facilities and traverses the Work Area as much as possible. This may be accomplished by position the HEPA filtered fan unit(s) at a maximum distance from the worker access opening or other makeup air sources.
F. Vent HEPA filtered fan units to outside of building so that:
1. At no time shall the negative pressure ventilation units exhaust within 40 feet of a receptor, or adversely affect the air intake ports, louvers, or entrances for the building or adjacent buildings.
2. Heavy duty ducting or equivalent, or larger, shape and dimension as that of the negative pressure ventilation exhaust port shall be used to exhaust to the outside of the structure.
3. All ducting shall be sealed and braced or supported to maintain airtight joints.
G. Should it not be feasible for the Contractor to exhaust to the building exterior, the following alternative is possible:
1. Vent each HEPA filtered fan unit to inlet of second unit, compatible with the primary 36 © AMBIENT GROUP, INC. -2002 PRESSURE DIFFERENTIAL & AIR FILTRATION SYSTEM
NYC-WTC 000155688
OCR can misread numbers and units. Confirm readings against the page image before using them.
Related records
Browse subjects →Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
Same-box records
NYC-WTC_000155525
Initial draft of the comprehensive scope of work required to safely clean 114 Liberty Street following environmental damage.
47 shared non-person entities · 1 shared topics · Same agency, volume and box · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗10 shared non-person entities · 1 shared topics · Same agency, volume and box · similarity 0.966
machine-extracted · confidence unavailable · Check page ↗Filed elsewhere
NYC-WTC_000155460
Submission of a preliminary scope of work document for safely cleaning the 114 Liberty Street building.
48 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000155168
Draft cleaning procedures and contract documentation for 114 Liberty with minor revisions, shared with EPA for review and comment.
8 shared non-person entities · 1 shared topics · similarity 0.968
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000138892
Forwarding draft cleaning procedures for 114 Liberty Street to EPA for review and comments.
8 shared non-person entities · 1 shared topics · similarity 0.967
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000154680
Application form submitted to the Department of Environmental Protection for notification of an asbestos inspection project.
14 shared non-person entities · 1 shared topics · similarity 0.967
machine-extracted · confidence unavailable · Check page ↗8 shared non-person entities · 1 shared topics · similarity 0.966
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000155394
Transmission of cleanup and environmental monitoring documentation for 114 Liberty post-WTC dust remediation project.
10 shared non-person entities · 1 shared topics · similarity 0.966
machine-extracted · confidence unavailable · Check page ↗10 shared non-person entities · 1 shared topics · similarity 0.966
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000162906
Document tracking the chain of custody for environmental monitoring samples at 114 Liberty Street on February 7, 2003.
10 shared non-person entities · 1 shared topics · similarity 0.966
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000104853
Facsimile cover sheet transmitting documents regarding environmental work at 102 Greenwich Street.
13 shared non-person entities · 1 shared topics · similarity 0.966
machine-extracted · confidence unavailable · Check page ↗More like this page
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000155525
Initial draft of the comprehensive scope of work required to safely clean 114 Liberty Street following environmental damage.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000155460
Submission of a preliminary scope of work document for safely cleaning the 114 Liberty Street building.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.961 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000155525
Initial draft of the comprehensive scope of work required to safely clean 114 Liberty Street following environmental damage.
Similarity score 0.961 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.961 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Buildings in this record
Machine-extracted building matches; verify each source. Buildings, never households.
- 114 Liberty Street · 9 pages · confidence 0.15 · verify page 1
- 114 UBERTY ST · 1 pages · confidence 0.15 · verify page 2
Others also read
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000155460
Submission of a preliminary scope of work document for safely cleaning the 114 Liberty Street building.
Cited alongside this record in an Ask answer
NYC-WTC_000155525
Initial draft of the comprehensive scope of work required to safely clean 114 Liberty Street following environmental damage.
Cited alongside this record in an Ask answer
Cited alongside this record in an Ask answer
NYC-WTC_000134132
US EPA Region 2 letter dated November 15, 2005, confirming completion of environmental review for abatement plans at 133-135 Greenwich Street.
Cited alongside this record in an Ask answer
NYC-WTC_000134871
EPA Region 2 letter regarding revised environmental work plan submission for two buildings including asbestos, health, and safety assessment components.
Cited alongside this record in an Ask answer