December 17,2002 114 LIBERTY STREET REMOVAL OF DUST, DEBRIS, AND CONTAMINATED MATERIALS

"RAM AIR 2M" as manufactured by Aramsco of Thorofare, NJ, or "Environmental Ltd., 300" as manufactured by Torchcross Agency Environmental, Hagerstown, MD or approved equal.

PART 3 - EXECUTION

3.01 PRESSURE DIFFERENTIAL ISOLATION:

A. The Contractor shall coordinate this item with the Building Owner at the commencement of work.

B. In ail areas, an alternate ventilation system must be installed. Portable Air Filtration Devices, capable of moving large quantities of air through a HEPA (High Efficiency Particulate Air filter capable of 99.97% efficiency at 0.3 microns) are to be installed. Each unit shall be serviced by a dedicated minimum 115V-20A circuit with ground fault circuit interrupter (GFCI) supplied from temporary power supply installed under requirements of Section 06, Temporary Facilities. Do not use existing branch circuits to power fan units.

C. Provide brand new AFDs, or provide on-site certificate of the HEPA filters. Certify that the AFDs have been tested via the DOP smoke challenge procedure and shall conform to GSA's Federal Standard 2096; ANSI N101.1: and MIL-F 51068E, as published bythe US Army.

D. The Contractor shall size each zone area, provide the number of AFDs to guarantee no less than four (4) complete air changes per hour during contaminated dust and debris removal and clean-up.

1. Portable AFD use and positioning shall conform to ANSI Z9.2 and is to be coordinated with Ambient Group, Inc.

2. The Contractor shall provide a minimum of one (1) additional AFD unit for each Work Area as a back-up.

E. Locate fan unit(s) so that makeup air enters the Work Area primarily through decontamination facilities and traverses the Work Area as much as possible. This may be accomplished by position the HEPA filtered fan unit(s) at a maximum distance from the worker access opening or other makeup air sources.

F. Vent HEPA filtered fan units to outside of building so that:

1. At no time shall the negative pressure ventilation units exhaust within 40 feet of a receptor, or adversely affect the air intake ports, louvers, or entrances for the building or adjacent buildings.

2. Heavy duty ducting or equivalent, or larger, shape and dimension as that of the negative pressure ventilation exhaust port shall be used to exhaust to the outside of the structure.

3. All ducting shall be sealed and braced or supported to maintain airtight joints.

G. Should it not be feasible for the Contractor to exhaust to the building exterior, the following alternative is possible:

1. Vent each HEPA filtered fan unit to inlet of second unit, compatible with the primary 36 © AMBIENT GROUP, INC. - 2002 PRESSURE DIFFERENTIAL & AIR FILTRATION SYSTEM

NYC-WTC_000155564

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000155564Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →