EMTEQUE October 18, 2002
Krish Radhakrishnan, P.E.
Director. Environmental Compliance
Asbestos Control Program
NYC Department of Environmental Protection
59-17 Junction Boulevard. 8“” Floor
Flushing. New York 11373-5108
RE; Ventilation System Inspection; 330 Rector St.; 395 South End Ave; 45 Wall St
EMTEQUE Project No. 0210-0629
□ear Mr. Radhakrishnan;
We visited the subject locations on October 18,2002 to determine the extent of visual WTC dust
contamination of various ventilation systems servicing the common/public areas at the subject
addresses. In summary, it appeared that the eir^iandlers and ductwork easily available for
inspection were either cleaned or did not reveal any fallout characteristics of lAfTC dust.
330 Rector St.
Laundry Roofn System-. Below grade outside air suppiy/exhaust louvers had normal amount of
lintZdust buildup, internal ductwork and fan housing were not available for inspection.
RooRop Air Handler (Services the building corridors)
The AHU was clean with new filters (there was minute amounts of possible WTC fallout around
'the internal insulation). Although the horizontal ductwork on the roof had dust buildup, it was from
a pre-existing condition (no signs of WTC dust). An associated wall supply diffuser was inspected
on the 12“* floor. Similarly, no visual evidence of WTC dust was present
39S South End Avenue (Gateway)
A supply and exhaust system was inspected in the basement. Access doors were available to
observe the ductwork upstream of the associated fans. No evidence of WTC fallout was noticed.
43 Wall St (residential building empty prior to 9/11)
Basement air handlers were relatively clean wrth no evidence of WTC dust. Outside air louvers
had dust buildup with some evidence of WTC dust although most of it was from pre-existing
conditions. Observed AHU serving the Club was clean (horizontal duct from wall could have WTC
dust but needs access panels for Inspection) (An apartment was inspected which had its window
open and did have WTC dust).
The above inspected addresses ventilation systems contained little or no visible WTC dust and in
my professional opinion the areas being served by these system are suitable for public
occupancy.