11.1.2 Site Preparation: To minimize possible contamination and damage, the ventilation
system/duct cleaning firm shall provide a negative pressure work area containment as
necessary during ventilation system remediation.
11.1.2.1 Negative pressure must be maintained by way of an attached external HEPA-
filtered air filtration device. The vacuum must provide at least eight (8) air
changes in the containment per hour.
11.1.2.2 The AHU servicing the area being cleaned must be shut down or zoned-off
and remain so during the cleaning process.
11.1.2.3 Only properly trained, authorized individuals may enter the work area while
cleaning is being performed.
11.1.3 System Access: Provide necessary access for cleaning and inspection of the ventilation
system.
11.1.3.1 Remove and poly bag difiusers if transport to decontamination area will be
through non-containment areas. Clean all grilles and diffusers. Thoroughly dry
grilles and diffusers prior to re-installing after cleaning.
11.1.3.2 Install service openings as specified in Appendix B in return air handling
systems as necessary to facilitate inspection and cleaning procedures. Access
points should not exceed fifty (50) foot intervals to accommodate procedures
and final inspection, unless otherwise deemed acceptable by the building
management or Environmental Cleaning Contractor.
11.1.3.3 The structural integrity of the ductwork shall not be significantly altered by the
installation of service openings (See APPENDIX B).
11.1.4 Duct Zoning: Ventilation system/duct cleaning firm will isolate sections of the
ventilation system if needed to facilitate cleaning.
11.1.4.1 Prior to cleaning, ventilation system airflow control devices may be
repositioned and zoning devices installed in diffusers and ductwork as
necessary to facilitate negative airflow from vacuum collection equipment and
to avoid contamination from entering the conditioned air spaces.
11.1.4.2 All zoning devices shall be removed and airflow control devices reset to their
pre-cleaning positions upon completion of cleaning in the work area they serve.
11.1.4.3 Zoning devices must be disposed of or cleaned free of contaminant debris or
other suitable measures employed to prevent cross-contamination prior to reuse
in other ventilation system areas.