sanitary sewer system is to be performed within two small areas
of The Coney Island Drainage Areas both loca-t^ between
Flatlands, Sheepshead Bay and Gerritsen^^^^^^t-area (G-2)
is bounded by Avenue X on the north, Batchelder Street on
the east, Voorhies Avenue on the south and E. 28th Street
on the west; the second area (G-12) is bounded by
Avenue U on the north, Bragg Street on the east. Avenue Y
on the south and E. 19th Street on the west (see attached maps) .
SMOKE TESTING PROCEDURE
1. Maps showing the location of the sewer lines and manholes
to be smoke tested within the area are prepared.
2. Summer is considered the best period to perform smoke
testing since groundwater levels are normally low. Rainy
and windy days are to be avoided.
3. Community Boards and both the Police and Fire Departments
are to be kept advxsed on a daily basis as to the nature
and time of the tests.
4. Residents are to be notified as to the nature and time
of the tests.
5. Two sections of sewer are tested simultaneously with
equipment set on the intermediate manhole of the sewer
sections being smoke tested.
6. A smoke generating device is activated and the smoke
is forced through the sewer system with a blower. The
area serviced by the sewer sections is thoroughly examined
during the test and all problems are recorded.
7. Photographs are taken of smoke coming out of the ground,
storm sewers, catch basins, roof drains, ate...(See
Exhibit 11 - "EXAMPLE PHOTOGRAPHS").
SMOKE TESTING NOTIFICATION
Smoke testing notices (Exhibit #2) will be slid under the
front door of every residence (if possible), posted in lobbies
of apartment houses and taped to light or telephone poles in
the project areas. Both Police and Fire Departments 'will be
informed of program activities.
DURATION OF SMOKE TESTING
It is estimated that 35,000 linear feet of sewer will be
smoke tested. Testing program will be conducted for a period
of approximately 10 days. Therefore, testing will commence
on or around 1984 and be completed by