Assessment, Cleaning and Restoration of HVAC Systems - ACR 2002

■ Cross Contamination Control - Suitable provisions shall be made to control contaminant discharge from the HVAC system and cross contamination into occupied space during the cleaning process. This may require temporary sealing of existing duct joints, seams and other system components. Level 2 Containment - Work Area Containment Without Decontamination Unit Level 2 Containment may be applicable to HVAC system cleaning in any building use classification when microbial contamination is known to exist within the system. In cases when microbial amplification covers a surface area greater than 5 square feet. Level 3 Containment must be used. Level 2 Containment is the minimum level of containment appropriate to a healthcare facility. All of the Level 1 Containment requirements apply to Level 2 Containment areas. In addition, the following protection actions are required under Level 2 Containment strategies: ■ Work Above Ceilings - Above ceiling work area must be completely isolated from occupied spaces within containment barriers utilizing 6-mil fire retardant polyethylene or equivalent. These barriers shall be sealed airtight where they meet the ceiling, floor, and walls. ■ Containment Area Floor - The containment shall have a two-layer floor utilizing 6-mil fire retardant polyethylene or equivalent. The floor material shall extend at least 6 inches (15.2 centimeters) up the containment side walls. The floor material must be sealed to side walls with two layers of duct tape in an airtight manner. Containment Area Access - A vertical cut in the containment side wall shall provide access into the containment area. This vertical cut must begin no less than 6 inches (15.2 centimeters) from the floor and must be at least 5 feet (12.7 centimeters) long. The entrance shall be entirely covered by two flaps (one on each side of the polyethylene). ■ Negative Pressure - The containment area should be kept under negative pressure at all times to the degree feasible. Negative pressure must be sufficient to prevent migration of particulate material out of the containment area. Exhaust from the device providing negative pressure must be HEPA filtered. If this device does not exhaust directly outdoors, it must be possible to verify that there is no leakage through or around the HEPA filter. ■ Dismantling — Interior surfaces of the containment enclosure must be wet-wiped or HEPA vacuumed before moving or dismantling the containment enclosure. Level 3 Containment - Work Area Containment with Single Chamber Decontamination Unit Level 3 Containment may be applicable to HVAC system cleaning in buildings where severe cases of microbial amplification or hazardous substances are known to exist within the HVAC system or indoor environment. Level 3 Containment is commonly the level of containment appropriate to healthcare facility cleaning projects, mcluding those where microbial contamination may not exist. All of the Level 1 Containment and Level 2 Containment requirements apply to Level 3 Containment areas. In addition, the following protection actions are required under Level 3 Containment strategies: ■ HEPA-filtered negative air machines may be utilized as a supplement to containment techniques described herein to control ambient airbome particulate levels.

Page 21

NYC-WTC_000139930

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000139930Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →