CVYATC ASSOCIATES INC.
Ambient Air Sampling
To: Related Management Company
Subject: Summary of Ambient Air Sampling to Date
Re: Tribeca Tower
From: Fred Burkhardt
Date: December 11, 2001
The following is a brief summary of the observations, real-time monitoring, and ambient air
sampling performed at Tribeca Tower to date.
Apartment Visual Inspection
ATC visually inspected 406 units for accumulated dust and/or debris consistent with material
that from ATC's experience emanated from the collapse of the World Trade Center Buildings.
Thirty-four units were inaccessible or the occupants refused access and were not inspected.
Of the 406 units inspected, ATC did not observe any dust and/or debris accumulations that in
ATC's opinion was consistent with widespread deposition of material that emanated from the
collapse of the World Trade Center Buildings. However, ATC observed adjacent to open
windows in four units, limited dust accumulations (no debris) although inconsistent with material
that emanated from the collapse of the World Trade Center Buildings present nonetheless.
Asbestos Air Sampling via TEM
ATC collected a total of 60 common area and 149 residential unit samples to ascertain the
presence or absence of airborne asbestos. All samples were collected and analyzed in
accordance with the AHERA Transmission Electron Microscopy (TEM) method as set forth at 40
CFR Part 763, Subpart E, Appendix A which provides resolution down to 0.5µ. structure size.
Of the total 209 samples collected, a single asbestos structure was detectable on only two
samples.
In the absence of a specific ambient air standard, ATC has selected as a criteria for acceptable
ambient air sample sets, the AHERA re-occupancy requirement following an asbestos
abatement action of an average of less than 70 asbestos structures per square millimeter (<70
s/mm2) per sample set. This criteria has been selected because the AHERA requirement is the
most stringent reoccupancy requirement available, and has been designed to be protective of
children following an asbestos abatement project.
Based upon analytical sample results for all samples recording levels well below the AHERA
clearance requirement, it is ATC's opinion that the ambient air samples collected throughout the
building are representative of the ambient conditions at the time of testing and that the areas
tested meet an acceptable criterion for re-occupancy