DEC-12-2001 17:48 NYC D.E.P. PUBLPC AFFAIRS
ACTS
ACTS, CRAMTS AND TBAT%.A SABZTY
iii Thopsoa ■t., 0 23
Now York, NY 100i2-2086
23,2/177-QOca
n-x►eLl 1ACTi$YCR68. a0a
hefts //«wr.sasewi.aw/aaa
Joel R. Xupf.riosn, Req.
Executive Director
New York E}svironmental Law a Just3C! Project
315 Broadway - Suite 200
plow York NY 1000?-.121 December 11, 2001
Dear Joel K pfermsn,
I have reviewed the December 9, 2001 report an asbestos sampling
done by Ed Olmsted, cIv, at 105 Duane street.
i concur with Mr. Olmsted'a conclusion tbAt the eamle taken from
the air diffuser in the loth floor public hallway .$.ewe levels of
asbestos well above the recommended limit of 2.000 structure per
square centimeter.
I also concur that the finding of 555,000 asbestos structure per
square eeatim.ter is a clear %ndication that the ventilation
system should be cleaned by a professional duct cleaning compafY
using vacuum and cleaning equipment designed fog asbestos
dseontu tnation. z would add that the work moat be done by
trained and certified asbestos abatement workers who can prevent
contamination of other parts of the building while they work.
2 also would add that this single sampLe should be followed up by
other samples taken from other locations in the ventilation
system.. This sampling must be undertaken immediately because
asbestos fibers in ventilation systems are likely to deposit
throughout the building. The reading of 740 asbestos structures
is high enough
per square centimeter on the living room table tophazardous.
to cause concern that further deposition could be It
levels
the elsani~i is delayed until many spartmenti attain pcneritially.
requiring abatement, the cost of cleanup will rice a
It is also 113e1 that there are already apartments in the
building in which the asbestos duct levels are much higgher.
These locations are most likely to be those in which the air is
supplied by diffusers that are closer to the ventilation system's
air intakes and filters. people living in these apartments may
be at risk now.
R ctfully
;;~ c r-;
tsoaona Rossol, 14.S., M.P.k. ,
industrial hygienist
1212 637 3561 P.06