Asbestos Abatement Technical Specifications
For 130 Cedar Street, New York, NY
a) Critical barriers shall be placed on all windows and openings in the
• work area. These shall be sealed and remain in place until final air
clearance testing has been completed.
b) The work area shall be pre-cleaned with HEPA vacuums, as well as
wet wiped where necessary, as directed by the Industrial Hygienist or
foreman assigned to the project.
c) Two (2) layers of 6-mil, fire retardant polyethylene sheeting shall be
placed on floors and walls and ceilings In order to provide protective
barriers and to achieve negative air pressure inside the work area.
d) Negative air filtration equipment of sufficient quantity and capacity
shall be determined on a per job basis. A minimum of 0.02 inches
water column shall be achieved prior to the start of any abatement
work. The capacity shall be enough to cause a complete air change
or total air filtration within the work area four (4) times per hour.
4.4 Decontamination Chamber Construction/Maintenance:
a) In work areas where it is required, a three (3) stage decontamination
(decon) chamber shall be constructed. This shall take place prior to
any work being started in any area.
b) The chamber shall be composed of a series of three (3) rooms/spaces
• set up in a consecutive arrangement from the work area to the outside
atmosphere. If required, a decontamination trailer shall be provided to
the workers and placed In an Isolated position in the uncontaminated
environment.
c) The first, innermost room of the decon chamber shall be designated
as the dirty or contamination room. It will be located at the closest
proximity to the enclosed work area and separated by an airlock. This
in turn shall be attached to a shower room by an air lock to prevent
fiber release. This shower room, which the workers shall use to
decontaminate themselves of all remaining asbestos fibers when
exiting work area, shall be attached to the clean room/outer room. The
clean room outer room shall be used as the entrance to the actual
decon chamber. It is here where street clothes and uncontaminated
personnel protective equipment shall be accessed.
d) Air locks used to separate the rooms shall be composed of fire-
retardant, plastic doors and weighted to prevent contaminated air from
escaping into the environment.
e) A minimum of two (2) layers of fire retardant, polyethylene shall be
used for construction of a decontamination unit inside the work area,
and a two (2) layer ceiling shall be used to protect the Integrity of the
decon unit.
f) The decon chamber doors shall be of sufficient height and width to
enable replacement of equipment that may fail during work
Prepared by JLC Environmental Consultants, Inc. Project No. 04-3271 Page 16