Rose Associates
JLC Project # 01-2089
September 18, 2001
page 2 it SarnplinQ Analysisand Procedure
Introduction
Air sampling is defined as the process of measuring the filter content of a known volume
of air
eniralned on a filter membrane over a specified period of time. Each sample is
cross-referenced by
field designation and a JLC lab internal code to ensure proper, consistent handling
through a chain
of custody, Sample preparation takes place within an HEPA filter clean bench to avoid any pocclblc
contamination.
Methodology
Test procedures for these samples conform to the National Institute of Occupational Safety and
Health (NIOSH) standards.
;l,
Air sampling was conducted at a level approximating the breathing zone of persons anticipatpri to
be present in the area during normal operations. Samples collected should represent the area's
typical airborne fihr►r concentration.
All samploc wore collected on fully exposed 25 millimeter, 0.8 micrurrieter (pm) cellulose ester
membrane air sampling cassettes with conductive cowl.
Analytical Procedures
Al oeotion of the filter approximating twenty-five percent of the total filter was removed and
placed on
a ,pre-cleaned microscope slide and then exposed to approximately 250 microliter (pl) of acetone
vapor. A single 3.0 - 3.5 pl drop of triacetin was applied and a clean #1.5 cover slip was placed
upon the filter. The prepared slide was then heated on a slide heater until clarity allowed analysis to
he conducted,
A►rlalysis was accomplished utilizing a Phase Contrast Microscope in accordance with NIOSH 7400
method, counting lute "A."
Phase Contrast Microscopy
JLC Environmental's laboratory uses an Olympus BH-PC Phase Contrast
equipped with a Walton-Beckett Oraticule, Samples were analyzed by firstMicroscope, (PCM)
dissolving the filter
through a chemical process (described above) and then counting the fibers with PCM at 400x
magnificatipn. Phase contrast Increases the light contrast between the object and the
thus enhat~cing the microscopist's ability to coo fibers. Normally, 100 microscopic fieldsbackground,
or 100
fibers are counted, whichever occurs first,
Analytical Results
The "Su.umrnary of Analytical Results" represents the results of the analysis of the samples.
The
PCM limit of reliable quantification is less than 0.01 fibers/cubic centimeter (f/cc) of air, If final tests
do not meet these requirements, the entire work site must be re-cleaned and re
-tested,