REPORT OF ANALYSIS
Westchester County Department of Labs and Research 2 Dana Road Valhalla, New York
Agency: New York City DEP DWQC Sample FIELD BLANK
Distribution Laboratory
96-05 Horace Harding Ex.
Corona N.Y. 11368 Sample FBD
Dr. Ian Hurley ID of Source:
Received BH Collection 11/22/2001 AT
Bottle p1145,q414 Submitted 11/22/2001 AT 9:40:00
Collected By: LAB Sample Type: POT_DW
Comment: PWS No.: Source Code:
Type Descriptor:
Sample chilled on arrival? : YES
Report
Sample No. AD28662
Method Test Description Results Units MDL Analyzed on Validator
Organics
GCMS Scan For LI s
Other unknown compounds ug/L 12/7/2001 DLV
The GCMS scan, from 35 to 550 amu, does not reveal the presence of unusual compounds.
The recovery for the Surrogate Standard in this sample was 89%. Recoveries for 9 of the 44 compounds in the LCS
Standard were outside of their acceptance ranges. The chromatogram reveals contamination which has been
identified to be from the TurboVap concentrator.