NYC 9/11 Public Portal Document
REPORT OF ANALYSIS
Westchester County Department of Labs and Research 2 Dana Road Valhalla, New York
Agency: New York City DEP DWQC Sample 3
Distribution Laboratory
96-05 Horace Harding Ex.
Corona N.Y. 11368 Sample 3
Dr. Ian Hurley ID of Source:
Received EP Collection 11/23/2001 AT
Bottle Q315,446.P1134,1140,C762 Submitted 11/23/2001 AT
Collected By: VASSILEV Sample Type: POT_DW
Comment: PWS No.: Source Code:
Type Descriptor:
Sample chilled on arrival? : YES
Report
Sample No. AD28677
Method Test Description Results Units MDL Analyzed on Validator
EPA94 Molybdenum <MDL ug/L 50.0 12/20/2001 PAD
EPA79 Potable Metals Digestion Completed 11/26/2001 PAD
SM18 Tin <MDL ug/L 100 1/2/2002 PAD
Organics
GCMS Scan For Unknowns
Other unknown compounds ug/L 12/7/2001 DLV
The GCMS scan, from 35 to 550 amu, does not reveal the presence of unusual compounds.
The recovery for the Surrogate Standard in this sample was 58%. Recoveries for 9 of the 44 compounds in the LCS
Standard were outside of their acceptance ranges. The chromatogram reveals contamination which has been
identified to be from the TurboVap concentrator.
Approved Pam Dilsizian QA Officer Date Approved: 1/2/2002
Environmental Laboratories emailed Original 1/2/2002
NYS ELAP # 10108 Page 2 of 2
NYC-WTC_000070817
OCR can misread numbers and units. Confirm readings against the page image before using them.