TECHNICAL REPORT
Indoor Air Quality Survey
Department for the Aging
2 Lafayette Street Floors 6, 8 and 16
January, 2006
Building Information :
Maintained by DCAS
Floors under investigation: 6, 8, 16
Thermal Comfort and Ventilation:
Aiea/Swlion T R.H CO2 CO
C‘F)^ <%)i (ppni) <ppin)
6th floor Info & referral 80 21 850 ND
unit
Sth floor Print shop by 78-79 18.5 607 ND
storage shelves
16th floor Near Ana 77 21 700 ND
Negron
workstation
ppm = Parts per million
% = Percentage
‘’F= Degrees f ahienhcit
ND= Not Detected
N/A= Not applicable
ASHRAE Recommended Comfort Guidelines:
Relative Humidity Winter Temperature Summer Temperature
30% 68.5-76.0°F 74.0-80.0°F
40% 68.5-75.5°F 73.5-79.5°F
50% 68.5-74.5°F 73.0-79.0°F
60% 68.0-74.0°F 72.5-78.0°F
CO2= 1,000 ppm (upper limit)
OSHA Permissible Exposure Levels (ppm)
Carbon monoxide (CO): 35 ppm
CITY_21MC100_003363344
NYC-WTC_000456099