NYC-WTC_000453548–000453579OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
• 24 hour 2.5 particulate sampling per the EPA’s Federal Reference Method (I KM ) ’ • To Be Completed
Airborne Asbestos Levels
Another criteria established to measure the “indoor air quality” of the WTC affect on the schools “indoor air quality” was also based on the federal standard for asbestos exposure under OSHA, the Occupational Safety and Health Act, which is used to protect workers on-the-job. The standard is .1 fiber per cubic centimeter averaged over an eight-hour day. The EPA is using the school re-entry standard in tests around the World Trade Center.
To determine school asbestos levels, air filters are collected from monitoring equipment through which air in the school building has passed and viewed through a microscope. The number of structures - material that has asbestos fibers on or in it - is then counted. The measurements must be 70 or fewer structures per square millimeter before children are allowed inside under the federal standards. To be as protective as possible. The BOE has environmentally cleaned the schools building’s to the extent that testing to zero asbestos fibers is required
The environmental cleanup program and the testing protocol are summarized in the following section.
AMBIENT AIR AND DUST SAMPLING PROTOCOL
The New York City Board of Education (BOE) in an effort to address concerns regarding Indoor Air Quality (lAQ) and potential asbestos contamination of the ambient air at the affected schools following the World Trade Center (WTC) tragedy and associated clean up work, established the following lAQ and ambient air monitoring/assessment protocol:
ASBESTOS To address the concerns regarding the potential of asbestos contamination of the ambient air, daily air testing and analysis was performed, including Saturdays and Sundays, inside and outside the affected school buildings.
AMBIENT AIR AND DUST SAMPLING PROTOCOL The duration of all ambient air samples was approximately 4 hours and the total air volume sampled at each location was approximately 1800 liters. All ambient air samples collected were analyzed via Transmission Electron Microscopy (TEM) in accordance with the methodology of the AHERA Final Rule. Results from samples collected each day were reported verbally, no later than Sam the
® The PM2.5 FRM is a filter based sampling method whereby one 24-hour sample was collected at various indoor locations on a daily basis. DOE00048139.DOC Appendix 1 - Page 6
CITY_21MC100_011284777
NYC-WTC_000453553
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000250253
ATC cost estimate letter for environmental services at six schools affected by 9/11.
16 shared non-person entities · similarity 0.942
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000250241
Laboratory report page with OCR-garbled content; appears to be environmental test results related to PS 89M.
16 shared non-person entities · similarity 0.941
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000278790
New York Council report on retrofitting HVAC systems at Ground Zero for IAQ.
32 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000322244
Consulting report cover page for HVAC retrofitting and air quality at Ground Zero.
22 shared non-person entities · 1 shared topics · similarity 0.987
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000276036
Document discussing lessons learned in children's environmental health related to Ground Zero sites.
27 shared non-person entities · 1 shared topics · similarity 0.957
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000455806
Safety and health survey of a DOE office space and HVAC system following employee complaints at 52 Chambers Street.
9 shared non-person entities · similarity 0.947
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000236896
Draft protocol document outlining daily ambient air and dust sampling procedures for PS/IS 89 following the World Trade Center tragedy.
16 shared non-person entities · similarity 0.946
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000319809
Document describing MS/PS 85M occupancy and recovery operations related to WTC.
16 shared non-person entities · similarity 0.943
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385830
protocol for ambient air and dust sampling inside PS 89 Manhattan following WTC cleanup.
16 shared non-person entities · similarity 0.942
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000274908
Draft ambient air/dust sampling protocol for asbestos at Stuyvesant High School.
15 shared non-person entities · similarity 0.942
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000145027
Notice from NYC Law Department instructing staff to preserve World Trade Center documents for potential legal actions.
16 shared non-person entities · 1 shared topics · similarity 0.941
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385871
Ambient air and dust sampling protocol for High School for Leadership & [name] (M 894).
16 shared non-person entities · similarity 0.941
machine-extracted · confidence unavailable · Check page ↗Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000278790
New York Council report on retrofitting HVAC systems at Ground Zero for IAQ.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000322244
Consulting report cover page for HVAC retrofitting and air quality at Ground Zero.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385841
Ambient air and dust sampling protocol for PS 150 Manhattan after WTC events.
Similarity score 0.976 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000289653
Review and summary of asbestos-related air and dust testing after WTC collapse; clarifies OSHA/settled dust guidance.
Similarity score 0.976 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385851
Draft ambient air sampling protocol for PS 150 Manhattan with lAQ considerations.
Similarity score 0.975 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000320107
Correspondence addressing asbestos monitoring data and interpretation of OSHA/EPA findings related to WTC area.
Similarity score 0.974 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000278790
New York Council report on retrofitting HVAC systems at Ground Zero for IAQ.
Similar indexed content
NYC-WTC_000322244
Consulting report cover page for HVAC retrofitting and air quality at Ground Zero.
Similar indexed content
NYC-WTC_000276036
Document discussing lessons learned in children's environmental health related to Ground Zero sites.
Similar indexed content
NYC-WTC_000455806
Safety and health survey of a DOE office space and HVAC system following employee complaints at 52 Chambers Street.
Similar indexed content
NYC-WTC_000236896
Draft protocol document outlining daily ambient air and dust sampling procedures for PS/IS 89 following the World Trade Center tragedy.
Similar indexed content