Methodology Approach to the WTC “Indoor Air Quality Problem”

For the New York City Board of Education Schools affected by the WTC collapse the following HVAC engineering approach for problem evaluation was developed.

• Evaluation of HVAC systems by reviewing design documents and site equipment audits to determine type and configuration of the schools HVAC components. • Determination of ventilation standards ventilation system requirements to ensure air quality (cleanliness) and ability of the existing HVAC components to meet the desired level of “indoor air quality”. • Determination of particulate matter criteria to establish the required level of “indoor air quality”. • On-site inspections of actual conditions and present HVAC filtering equipment and efficiency ratings. Verify that the present design is proper and that the installation complies with the design. • Determination of system rehabilitation requirements to perform to design standards and operating requirements. Verify that the installation is subject to proper maintenance and operating procedures. • Verify that the existing building systems can be modified in the “as-is” condition or can retrofitted within the program schedule and criteria established by the BOE. • Develop corrective actions required to achieve the program goals and define the physical space requirements or constraints hindering the achievement of the program. • Baseline Air Testing of present HVAC equipment to determine existing operating parameters including: Supply CFM, Return CFM, Outdoor Air CFM Fan RPM and operating characteristics i.e. type and size Motor HP and operating characteristics, i.e. running amperage Static Pressure readings throughout the system

• Comparison of operating Air Testing Data to Design Requirements and determination of system to accommodate higher filtration and higher system static.

• Selection of higher efficiency MERV rated filters to increase system particulate filtration efficiency and air cleaning of VOC’s .

• Evaluation of the location of the existing HVAC outside air intakes and ability to provide additional pre-filters to protect higher efficient after filters. • Evaluation of the location of the existing HVAC outside air intakes and outdoor air VOC contaminants to establish the need for charcoal activated carbon filters for odor and VOC control.

DOE00048139.DOC Appendix 1 - Page 12

CITY_21MC100_011284783

NYC-WTC_000453559

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000453559Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →