Exceedance report, AFD exhaust, 4 Albany Street, Mar 2005

Machine-extracted title · confidence 37%

Exceedance notice for airborne asbestos fibers from AFD exhaust at 4 Albany Street; March 14, 2005 event.

NYC-WTC_000450386
Page image
Scanned page image, NYC-WTC_000450386
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

RJ LeeG'rowp, Inc. Exceedance Report

Date of Exceedance: March 14, 2005 Analyte: Airborne Asbestos Location: (South) AFD Exhaust. Carlisle Street Sidewalk Bridge Concentration: 88.2 s/mm^ Trigger Level: 70 s/mm^

Summary of Event:

On Monday, March 14, 2005 sampling for airborne asbestos fibers was conducted at the (South) AFD Exhaust at the Carlisle Street Sidewalk Bridge location outside the 4 Albany Street Building. The sampling was initiated at 2:47PM on March 14, 2005 and concluded at 10:47PM that same day (total collection time: 480 min.; sample volume: 2400 liters). The sample was received at the RJ Lee Group laboratory (Monroeville, PA) on Wednesday, March 16 and analyzed that evening using the AHERA TEM method. The results from the analysis of the sample reported an asbestos fiber concentration of 88.2 s/mm“.

The exceedance was reported by the laboratory via telephone to Mike Campbell on Wednesday night and the results were e-mailed to all parties immediately. The DEP and EPA were notified, via telephone, of the exceedance on the morning of Thursday, March 17 and a conference call to discuss the exceedance was held at 12:30PM that afternoon.

Corrective Action: The air filtration device (AFD) that had the exceedance was located on the Sth floor. During the 2”** shift on Monday, March 14, the shift of the exceedance, there was no work performed on this floor other than regular filter maintenance of the AFD’s. Regular filter maintenance involves replacing the pre-filter and visual inspection of the secondary filter, ff at the time of the routine maintenance the secondary filter is visually dirty, it is replaced. During the routine filter maintenance of the AFD in question, the secondary filter was visually observed to be acceptable and therefore was not replaced.

Upon notification of the exceedance this AFD was immediately shut down, the intake was sealed with poly and the slinky hose was taped shut and the spare AFD on the 8* floor was initialized. Since all abatement and final cleaning activities had previously been completed on this floor and encapsulation of the floor had taken place only hours before the report of the exceedance, there was no work stoppage.

Subsequent investigation of the exceedance included a visual inspection of the AFD, a review of PAL’s (the abatement contractor) site log along, and interviews of the site management team. Visual inspection of the AFD showed duct tape repairs and a stretched, uncoiled, section of the “slinky” exhaust hose. The HEPA filter appeared to be seated properly. The PAL site log did not have any information regarding this AFD during the shift in question, however PAL representatives stated that during routine fdter maintenance a breech in the “slinky” hose was found and a repair, utilizing spray glue and duct tape was performed. This repair reportedly required the AFD to be shut down for approximately 10 minutes.

No definite cause of the exceedance has been identified, other than the reference to the slinky exhaust hose repair reported, to have occurred during the sampling time frame of this exceedance.

Attachments: Report sLimmary - AHERA TEM Air Results for March 14, 2005 Figures - Air sampling maps of asbestos TEM locations for March 14, 2005

Submitted By: Mike Campbell Date: March 22, 2005 Final

CITY_21MC100_0 03244053

NYC-WTC_000450386

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000450386Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000428658

Airborne asbestos exceedance at AFD Exhaust; concentration 88.2 s/mm3; March 14, 2005.

Similar indexed content

NYC-WTC_000426084

Airborne asbestos exceedance at AFD Exhaust; concentration 88.2 s/mm3; March 14, 2005.

Similar indexed content

NYC-WTC_000425961

Final TEM air analysis report for AFD exhaust, February 26, 2005 exceedance.

Similar indexed content

Asbestos air exceedance report, Feb 2005

NYC-WTC_000234319

Lab report documenting an airborne asbestos fiber concentration exceedance at the AFD Exhaust BL6 location on February 26, 2005.

Similar indexed content

Compare copies and versions →