highest count for any one species being 500 CFU/in^ and a total sum of 1,600 Cf l /in ’.
Mold
Interpretation of these results cannot be completed using standard practices. The
standard practice for determining if an indoor environment is being impacted by mold is
to compare the species and concentration of indoor mold samples to outdoor mold
samples that were collected during the same sampling event, however, based on the data
received it appears that there were no outdoor samples collected for comparison. Using
an approach that is less desired than the standard practice, the following conclusions can
be drawn from the data. Although there are no specific standards, the general rule of
thumb for interpreting mold data usually considers concentrations greater than 10,000
CFU/in^ to be the low end of the spectrum for beginning additional mold investigation,
and concentrations greater than 100,000 to signify “mold contamination”. The
concentrations for each individual species, as well as the total sum for all species was
well below 10,000 CFU/in‘. In addition, the fungi species observed are the most
frequent species identified and are ubiquitous in the environment, both outdoors and
indoors. This leads to an overall conclusion that the concentration and species of mold
present are typical of an indoor environment. More information can be obtained from the
American Industrial Hygiene Association at
http://www.aiha.org/GovemmentAffairs-PR/html/oomold.htm.
Bacteria
The interpretation of the bacteria results has the same limitations as discussed above for
mold, namely that indoor concentrations should be compared to outdoor concentrations.
There is less information about indoor concentrations of bacteria than there is for mold,
however one report littp://www.atsdr.cdc.gov/HAC/PH/Vfranklinfungi/ief pkhtml from
the Agency for Toxic Substances and Disease Registry (ATSDR) reports that
concentrations of Bacillus at 1,000 CFU/in2 and Staphylococcus at 2,400 CFU/in2 are
low and most likely are a normal part of the bacterial load. The concentrations reported
from 114 Liberty are much lower than these values. Therefore, even though there was
not an appropriate outdoor sample collected for comparison, it can be concluded that the
bacterial concentrations reported from the one indoor sample that was collected are
typical of an indoor environment.