NYC 9/11 Public Portal Document

04/25/02 Liberty Mutual WTC IH Operations

• Clean the stairwell wall, ceiling, etc. surfaces with a biocide or chlorine solution.

• Require workers performing this stairwell cleaning to wear frill face respirators with tri-combination filters and full body coverings. This PPE is needed primarily to provide protection against biocide chemical spray or splatter

• Remediate microbial contamination throughout WTC 5 B4 and on B2 in the first room on the right room as you enter the loading dock from the J ramp (West) side, as well as any additional areas that may be identified moving forward. At a minimum the remediation should follow die NYC guidelines for mold remediation. This work should be performed under the over sigjit of an industrial hygienist. Tiberty Mutual is available to fulfill this role.

• Utilize a contractor with a broad experience remediating microbial contamination including both fungi and bacteria, especially fecal bacteria.

Conduct a review of at least dre following for any contractors being considered to perform die remediation:

• fungi/bacteria remediation work history experience

• fungi/bacteria remediation training and qualifications

• hazard communication program

• medical surveillance program

• respiratory protection program

• PPE programs

• Blood Borne Pathogens program

• waste handling plan

Tiberty Mutual industrial hygiene and medical consultation staff are available to assist in this review. It is highly recommended that this service be utilized.

Data Interpretation

The outdoor samples contained 27 and 173 spores per cubic meter of air. (cu.m.) These consisted of Amerospores and Cladosporium. The attached glossary describes the major fungal genii found .

The B4 Vault 1 and Kitchenette contained 322,667 fungal spores/cu.m. and 289,333 fungal spores/cu.m. These consisted of Aspergillus/Pcnccillium-likc spores and Basidiospores (refer to the attached glossary). These high levels are considered extremely high as they are in excess of 25,000 times the average outdoor level found on die sampling day/ These levels support the decision to: secure die space, treat entry into the space as a permit required entry, require Tyvek coveralls, gloves, and hill face respirators with the Tri Combination filters. PPE requirements may need to be modified after the viable fungi and bacteria sample results are available.

' The outdoor level found on the sampling day is typical for this area and time of year, per data posted on the American Academy of Alergy Asthma and Immunolog)" (AAAAI) web site.

2

CITY_21MC100_003254228

NYC-WTC_000437200

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000437200Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →