NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 3 pages

WTC 5 mold assessment follow-up, Apr 2002

Machine-extracted title · confidence 48%

Follow-up report to mold assessment; includes sampling methodology and initial results.

NYC-WTC_000244062–000244064
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

5 04/25/02 Liberty Mutual WTC IH Operations

• Clean the stairwell wall, ceiling , etc. surfaces with a biocide or chlorine solution.

• Require workers performing this stairwell cleaning to wear hill face respirators with tri-combination filters and full body coverings. Ihis PPE is needed pnmanly to provide protection against biocide chemical spray or splatter

• Remediate microbial contamination throughout WTC 5 B4 and on B2 in the first room on the right room as you enter the loading dock from the J ramp (West) side, as well as any additional areas that may be identified moving forward. At a minimum the remediation should foUow the NYC guidelines for mold remediation. This work should be performed under the over sight of an industrial hygienist Liberty Mutual is available to fulfill this role.

• Utilize a contractor witli a broad experience remediating microbial contamination including both fungi and bacteria, especially fecal bacteria.

Conduct a review of at least the following for any contractors being considered to perform the remediation:

• fungi/bacteria remediation work history experience

• fungi/bactena remediation training and qualifications

• hazard communication program

• medical surveillance program

• respiratory protection program (i

• PPE programs

• Blood Bome Pathogens program

• waste handling plan

Liberty Mutual industrial hygiene and medical consultation staff are available to assist in this review. It is highly recommended that this service be utilized.

Data Interpretation

The outdoor samples contained 27 and 173 spores per cubic meter of air. (cu.m.) 'Phese consisted of Amerospores and Cladosporium. The attached glossary describes the major fungal genii found .

The B4 Vault 1 and Kitchenette contained 322,667 fungal spores/cu.m, and 289,333 fungal spores/cu.m. These consisted of Aspergillus/Penecillium-like spores and Basidiospores (refer to the attached glossary). These high levels are considered extremely high as they are in excess of 25,000 times the average outdoor level found on the sampling day'. These levels support the decision to: secure the space, treat entry into the space as a permit required entry, require Tyvek coveralls, gloves, and full face respirators with the I'ri Combination filters. PPE requirements may need to be modified after the viable fungi and bacteria sample results are available.

’ The outdoor level found on the sampling day is typical for this area and time of year, per data posted on the American Academy of Allergy Asthma and Immunology (AAAAI) web site.

2

CONFIDENTIAL INSURANCE INFORMATION, CITY_21MC100_008007666 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000244063

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000244063Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →