Asbestos TEM analysis, World Trade Center, Sep 2001

Machine-extracted title · confidence 44%

TEM-based asbestos analysis for World Trade Center site, 09/17/01.

NYC-WTC_000431348
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

I ATC Environmental, Inc. 104 East 25th Street New York, New York 10010 NYC School Construction Authority Approved N.Y. State ELAP #10879 3'0-3 0 Thomson Avenue ACCREDITED NVLAP Lab Code # 1187 Long Island City, NY 11101 Report Date: 09/17/01

I ASBESTOS FIBER ANALYSIS BY TRANSMISSION ELECTRON MICROSCOPY (TEM) with Fiber Identification by Selected-Area Electron Diffraction (SAEDl and Energy-Dispersive X-RAY Spectroscopy (EDS) Method: AHERA Final Rule, EPA Federal Register (40 CFR, Part 763), Vol. 52, No. 210,. October 30, 1987

iample Identification Analysis Parameters

’rojecc/Site: World Trade Centerj NYj^TY TEM Sample No. :

I Personal Monitoring Date Received:_p92i2Z^ Grid Openings Analyzed: 10

I Project Sample No.; 034 Average Grid Opening: 106.00 ura

Air Volume: 100 liters Total Area Analyzed: 0.1124 nim2

I Filter Type: MCE 25 mm diam. Pore Size: 0.45 urn Analytical Sensitivity: 8.9 s/mm2 Effective Area: 38 5 rnm2 0.0343 s/cc

MFIBROUS PARTICULATES ANALYZED Number Observed CONCENTRATION

I Total .Single Matrix Total. Struct, Filter Air Fibers Bundles Clusters Struct. Struct >a5um Strucc/mtn2 Struct/cc ngm/m3

I Chrysotile Asbestos 1 3 0 1 5 2 44.5 0.1713 5652

Amphibole Asbestos 0 0 0 0 0 0 0.0 0.0000 0 I Ambiguous 0 0 0 0 0 0 0.0 0.0000 0

Total asbestos (includes ambiguous structures) 5 2 44.5 0.1713 5652

I Non~Asbestos No Identification 0 0 0 0 0 0 0 0 0 0 0 0 0.0 0.0 0 . oooo 0.0000 N/A N/A

I Totals (All Structures) The estimated uncertainty of this analysis is 1 standard deviation. 5 2 44.5 0.1713 N/A

Non-asbestos fiber i.d. (EDS/SAED): None detected I Amphibole Asbestos Type: None detected The Analysis was carried out in accordance with the approved TEM method. I This laboratory is in compliance with the quality specified for the method.

I Analyzed by: Report Reviewed by.

Marek Peysakhov Michael A. Gorycki, Ph.D. I Director of Electron Microscopy

I CITY_21MC100_010237405

NYC-WTC_000431348

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000431348Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →