NYC 9/11 Public Portal Document
Part V - Quality Assurance Project Plan
133-135 Greenwich Street/21-23 Thames Street
Airtek Project 05-0701 - September 29, 2005
secondary source standard. LCSs and/or LCS Duplicates arc typically performed as part
of each analytical batch for each methodology with the exception of asbestos, PMio and
PM2.5.
11.2.2.5 Laboratory Duplicate Laboratory duplicates are used to evaluate laboratory
preparation and analysis precision. These analyses are typically performed for inorganic
parameters only. Laboratory duplicates are typically performed at a frequency of one per
twenty samples.
11.2.2.6 Internal Standards Internal standards are used to assess the analytical accuracy,
precision, and stability. Internal standards are typically only used for organic analyses
and ICP/MS analyses. Internal standards are spiked into all samples and are considered a
sample-specific QC measure.
11.2.2.7 Standard Reference Materials Standard reference materials (SRMs) are used to
evaluate laboratory preparation and analysis bias for specific compounds in a reference
matrix. SRMs will be used for the asbestos analysis.
12.0 SAMPLE HANDLING AND CUSTODY REQUIREMENTS
Summaries of sample media, required sample volumes, preservation, and holding
time requirements for all samples are presented in Table 12-1. With the exception of
samples that are completed on Sundays, samples will be delivered to the laboratories via
Federal Express immediately after collection on ice (where required) with coolers under
custody seal or via courier service. Samples completed on Sundays will be shipped with
Monday’s shipment.
12.1 Sample Custody
Sample custody is addressed in two parts: field sample collection and laboratory
analysis. A sample is considered to be under a person’s custody if* the item is in the
actual possession of a person; • the item is in the view of the person after being in actual
possession of the person; • the item was in the actual physical possession of the person
but is locked up to prevent tampering; and, • the item is in a designated and identified
secure area.
12.1.1 Field Sample Custody
Sample handling is an important part of the field investigation program since samples
that are incorrectly handled can affect the quality of data. Sample handling begins at the
collection of the samples and continues until the sample has been analyzed. An over
riding consideration essential for the validation of environmental measurement data is the
necessity to demonstrate that samples have been obtained from the locations stated and
that they have reached the laboratory without alteration. Evidence of sample tracking
from collection to shipment, laboratory receipt, and laboratory custody (until proper
63
CITY_DEP_WORBY_CANNATA_SUBP_000070997
NYC-WTC_000423947
OCR can misread numbers and units. Confirm readings against the page image before using them.