CHAPTER 1—ASBESTOS CONTROL PROGRAM §1-92
(h) Openings made in the isolation barrier to accommodate these units
shall be made airtight. The units shall remain within the work area unless
located securely outside the building.
(i) Negative air pressure equipment shall be in compliance with ANSI Z9.2'
(1979), Local Exhaust Ventilation. '
(j) Negative air pressure systems shall be operated in accordance with
“Specifications and Operating Procedures for the Use of Negative Pressure
Systems for Asbestos Abatement,” Guidance for Controlling Asbestos-Con
taining Materials in Buildings, EPA Report Number 560/5-85-024 (1985).
(k) Negative pressure ventilation equipment shall be exhausted to the
outside of the building away from occupied areas.
(1) At no time shall the negative pressure ventilation unit exhaust
within 40 feet of a receptor or adversely affect the air intake ports, louvers,
or entrances for the building or adjacent buildings.
(2) Heavy duty ducting of equivalent, or larger, shape and dimension as
that of the negative pressure ventilation exhaust port shall be used to
exhaust to the outside of the structure.
(3) All ducting shall be sealed and braced or supported to maintain
airtight joints.
(1) Where ducting to the outside is not possible, a second negative pressure
ventilation unit compatible with the primary unit’s capacity shall be con
nected in series. The area receiving the exhaust shall have sufficient, non-re
cycling exhaust capacity to the outside of the structure.
(m) Carefill installation shall be done to ensure that the ducting does not
release fibers into uncontaminated building areas.
(n) Routine smoke testing, air monitoring and daily inspections shall be
performed by the Asbestos Handler Supervisor to ensure that the ducting
does not release fibers into uncontaminated building areas.
§1-92 Work Place Entry and Exit Procedures. The following procedures
shall be followed during the conduct of abatement activities on large asbestos
projects:
(a) Entrance procedures. (1) All workers and authorized visitors shall
enter the work area through the worker decontamination enclosure system.
(2) All individuals who enter the work area shall sign the log, located in
the clean room, upon each entry and exit. The log shall be permanently
bound and shall identify fully the facility, owner, agents, contractor(s), the
project, each work area and worker respiratory protection employed. The
log shall be available for examination during general business hours by the
Department, the owner and the workers.