NYC 9/11 Public Portal Document

(Srerc 104 East 25th St., 10th Floor New York, New York 10010 www.atc-enviro.com; 212.353.8280 Fax 212.353.8306 ASSOCIATES INC.

June 14 2002

Mr. Bernard P. Orlan Director, Environmental Health & Safety New York City Board of Education 28-11 Queens Plaza North Long Island Cily, NY 11101-4008 '

Re: Indoor Air Quality Assessment P.S.89M 201 Warren Street New York, New York 10282 ATC Project No. 15-19125-0297

Dear Mr. Orlan:

ATC Associates Inc. (ATC) is pleased to provide this report of indoor air quality (lAQ) measurements collected on June 13, 2002, at the referenced school. The New York City Board of Education (BOE) requested these measurements to evaluate air quality in the school building.

SCOPE OF WORK

ATC conducted this evaluation to assess the basic parameters of temperature, relative humidity, carbon dioxide (CO2) and carbon monoxide (CO).

ATC measured temperature, relative humidity, COj and CO with a Q-Trak® Model 8551, manufactured by TSI, Inc.

ATC measured concentrations of respirable particulates (PM2.5) with a Dust-Trak® Aerosol Monitor Model 8520, manufactured by TSI, Inc.

ATC measured concentrations of Total Volatile Organic Compounds (TVOCs) using a RAE Systems, Inc. MiniRAE® photoionization detector (PID).

Mr. Kevin Fitzpatrick, Environmental Technician, of ATC’s New York City office, conducted the assessment.

ATC’s findings and conclusions are based on a visual inspection, real-time environmental measurements and conditions present in. the school at the time of the assessment.

The assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy. The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.

CONFIDENTIAL, CITY_21MC1OO_OO3488585 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000411165

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000411165Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000175971

Report detailing indoor air quality measurements conducted at PS 89M to evaluate building air conditions following the WTC collapse.

Similar indexed content

IAQ report, P.S. 89M, May 2002

NYC-WTC_000369857

Indoor air quality report for PS/89M school, measurements collected May 22, 2002.

Similar indexed content

Compare copies and versions →