Mr. Bernard P. Orlan June 13, 2002 Indoor Air Quality Assessment Page 3 P. S. 89M . ATC Project No. 15-19125-0297 Real-Time Environmental Measurements

ATC collected seventy-nine (80) sets of real-time environmentaT measurements consisting of seventy (70) from inside the school building and ten (10) from outdoors. All five floors of the school building were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:01 A.M. and concluded at approximately 10:51 A.M. ■

Temperature

Indoor dry bulb temperature measurements ranged from 70.8 °F to 75.5 °F. Twenty-four (24) of the indoor measurements for temperature were below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 81.1 °F to 81.3 °F.

. Relative Humidity , _

The relative humidity indoors ranged from 49.6 to 61.2 percent. Three (3) of the indoor measurements for relative humidity were above the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 59.0 to 59.3 percent.

Carhnn Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 525 ppm to 1362 ppm. One (1) of the indoor measurements for CO2 was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 606 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1306 ppm (background level + 700 ppm). Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.

Carbon Monoxide' Concentration

Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 1 ppm for all collected readings.

Respirable Particulates HMys)

Respirable particulate concentrations* indoors ranged between 15 pg/m^ to 82 pg/m^. The average PM2,5 concentration for the entire school building was approximately 41 pg/m^. Eleven (11) of the indoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Thirty-two (32) of the indoor measurements were above the USEPA recommended concentration of 40 pg/m3 for sensitive individuals and children. The outdoor respirable particulate concentration measurements ranged betw^een 149 pg/m^ to 162 g/m3 with an average of 159 pg/m^.

CONFIDENTIAL, CITY_21MC100_003488575 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000411163

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000411163Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →