NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan March 18, 2002
Indoor Air Quality Assessment Page 3
P. S. 150M ATC Project No. 15-19125-0289
Reai -Timf Environmental Measurements
ATC collected forty (40) sets of real-time environmental measurements consisting of thirty (30)
from inside the school building and ten (10) from outdoors. All three floors of the school
building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 12:00 P.M. and concluded at
approximately T. 30 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 69.1.°F to 75.6°F. Five (5) of the
measurements were above the range of 68 to 75 °F (at 50 percent relative humidity) as
recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime
conditions). The outdoor temperature measurements ranged from 56.3 to 57.6°F.
Relative Humidity
The relative humidity indoors ranged from 37.5 to 50.1 percent. All of the measurements were
within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor
relative humidity measurements ranged from 56.3 to 59.0 percent.
CarbpnH2ioxide Cpncen^tion
Carbon dioxide concentrations indoors ranged from 491 ppm to 840 ppm. All of the CO2
measurements were within the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The maximum outdoor (background)
CO2 concentration was 428 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1128 ppm (background level -I- 700 ppm). Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator
of available outside makeup air. The primary source of CO2 indoors is occupant respiration.
The school building was occupied during ATC’s assessment.
CarbonMonmdde Concentration
Carbon monoxide concentrations were 0 ppm for the interior readings. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was
also 0 ppm for all collected readings.
Respirable Particulates (PM2,5)
Respirable particulate concentrations* indoors ranged between 45 pg/m^ to 79 pg/m^. Twenty-
four (24) of the indoor measurements were above the NPAAQS of 65 pg/m^ • All thirty (30) of
the indoor measurements were above the USEPA recommendation of 40 pg/m3 for sensitive
individuals and children. The average PM2.5 concentration for the entire school building was
approximately 70 pg/m^. The PM2.5 average concentration was above the USEPA
recommended concentration of 40 pg/m^ for sensitive individuals / children. The outdoor
CONFIDENTIAL, CITY_21MC100_003386212
SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000410537
OCR can misread numbers and units. Confirm readings against the page image before using them.