NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

Indoor air quality report, Feb 2002, PS 150M/PS 150M

Machine-extracted title · confidence 25%

ATC reports IAQ measurements at a NYC BOE school before re-occupancy, Feb 2002.

NYC-WTC_000300682–000300685
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document I

Mr. Bernard P. Orlan February 14, 2002 Indoor Air Quality Assessment Page 3 P. S. 150M ATC Project No. 15-19125-0289

Real-Time Environmental Measurements

ATC collected forty (40) sets of real-time environmental measurements consisting of thirty-three (33) from inside the school building and seven (7) from outdoors. All three floors of the school building were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 12:00 P.M. and concluded at approximately 1:30 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 72.5°F to 82.3°F. Twenty-five (25) of the measurements were above the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 41.9 to 42.6°F.

RelatiyeHumidity

The relative humidity indoors ranged from 11.0 to 16.7 percent. All of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 11.7 to 12.5 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 489 ppm to 927 ppm. All of the CO2 measurements were within the ASHRAE Standard 62-1999 recommended maximum concentrationiof <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 459 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1159 ppm (background level + 700 ppm). Levels above the reconunended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.

CarbmMonoxideCpncenp^ation

Carbon monoxide concentrations indoors were 0 ppms for the interior readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 1 ppm for all collected readings.

Respirable Particulates (PM2.5)

Respirable particulate concentrations* indoors ranged between 5 pg/m^ to 10 pg/m^. None of the measurements were above the NPAAQS of 65 ug/m^ 24-hour average concentration of , particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration for the entire school building was approximately 10 pg/m^. The PM2.5 average concentration was below the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children. The outdoor respirable particulate concentration measurements ranged from 8 to 12 pg/m3 with an average of 28 pg/m^.

CITY_21MC100_004151807

NYC-WTC_000300684

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000300684Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000375441

Indoor air quality measurements at P.S. 150M, school building prior to re-occupancy.

Similar indexed content

Compare copies and versions →