Indoor air quality report, HS for Leadership (Mar 2002)

Machine-extracted title · confidence 42%

ATC report of IAQ measurements at High School for Leadership, March 2002, for BOE.

NYC-WTC_000409958–000409962
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan March 19,2002 - Indoor Air Quality Assessment Page 4 H.S. for Leadership & Public Service (M8941 ATCPrpiectNpJ5U9125-0290 instantaneous readings were above the USEPA recommended concentration for sensitive individuals such as asthmatic people and children of 40 pg/m^.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentration

The TVOCs concentrations were 0 ppm inside the building. These concentrations were below the AIHA guideline for odor control of 1 ppm. The outdoor TVOC concentration was also 0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of COg, CO, and TVOCs were below applicable standards and guidelines. 2. One hundred and twenty-three (123) indoor measurement for temperature were within and four (4) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 3. Twelve (12) of the indoor measurements for relative humidity were below and one hundred fifteen (115) were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. 4. All of the indoor measurements for PMg.s were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration for sensitive individuals such as asthmatic people and children of 40 pg/m^. All of the outdoor measurements were below the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Three (3) of the twelve (12) instantaneous readings were above the USEPA recommended concentration for sensitive individuals such as asthmatic people and children of 40 pg/m^.

CONFIDENTIAL, CITY_21MC100_003387923 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000409961

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000409961Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000260023

IAQ measurements collected Mar 19, 2002 for BOE

Similar indexed content

NYC-WTC_000260018

IAQ measurements collected Mar 18, 2002 for BOE

Similar indexed content

NYC-WTC_000259941

IAQ measurements collected Mar 11, 2002 for BOE

Similar indexed content

Compare copies and versions →