Indoor air quality report, H.S. of Economics & Finance

Machine-extracted title · confidence 28%

IAQ measurements at school; BOE requested assessment.

NYC-WTC_000405261–000405264
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan June 25, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833)________ ATCProiectNo. 15-19125-0291 Real-Time Environmental Measurements

ATC collected one hundred and six (106) sets of real-time environmental measurements consisting of ninety-four (94) inside the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings were collected in the morning and in the evening. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 78.4 °F to 84.7 °F. Ninety-two (92) of the indoor measurements for temperature were above the range of 73 °F to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 83.3 °F to 89.6 "F.

Relative Humidity

The relative humidity indoors ranged from 39.8 percent to 56.3 percent. All of the indoor measurements for relative humidity were within ASHRAE recommended range of 30 to 60 percent for occupant comfort, 'lire outdoor relative humidity ranged from 60.1 to 64.0 percent.

CgrbonDioxideConcentrqtion

Carbon dioxide concentrations indoors ranged from 460 ppm to 849 ppm. All of the indoor measurements for CO2 were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) COi concentration was 529 ppm. Therefore, the maximum acceptable level of CO? at this location was 1229 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

CqrbptiMpnpxideConc^ration

Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. These concentrations were within the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm to 3 ppm.

Respirable Pariiculates (PM2,5)

Respirable particulate concentrations* indoors ranged between 12 pg/m^ to 112 pg/m^ with an average of 30 pg/m^- Nine (9) of the indoor measurements for respirable particulates were above the NPAAQS of 65 pg/m^ 24-bour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and above the USEPA recommended concentration of 40 pg/m3 for sensitive individuals and children. The respirable concentration outdoors ranged between 123 pg/m^ to 169 pg/m^ with an average of 150 pg/m- ■

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

CITY_21MC100_002365452

NYC-WTC_000405263

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000405263Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000396715

ATC IAQ measurements collected June 17, 2002 as part of BOE monitoring.

Similar indexed content

NYC-WTC_000396719

ATC IAQ measurements collected June 18, 2002 for BOE IAQ maintenance.

Similar indexed content

NYC-WTC_000385115

ATC IAQ measurements collected June 18, 2002 for BOE at the High School of Economics and Finance.

Similar indexed content

NYC-WTC_000385111

ATC IAQ measurements collected June 17, 2002 for BOE at the High School of Economics and Finance.

Similar indexed content

Compare copies and versions →