Mr. Bernard P. Orlan April 23, 2002 Indoor Air Quality Assessment Page 3 ITS, of Economics and Finance (M833)________ ATCProiectNoM5^191254)291 Real-Time Environmental Measurements
ATC collected ninety (90) sets of real-time environmental measurements consisting of eighty- one (81) inside the school building and nine (9) outdoors. Field data sheets are found in the Attachment. Readings began in the morning and concluded in the afternoon. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 70.4 °F to 85.9 °F. Three (3) of the indoor measurements were bellow , thirty-seven (37) were above, and forty one (41) measurements were within the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature ranged from 69.6 to 74.2 °F.
Rela^veJTumidify
The relative humidity indoors ranged from 33.2 percent to 41.2 percent. All of the indoor measurements for relative humidity were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 36.2 to 41.2 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 438 ppm to 1121 ppm. All of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) COy concentration was 742 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1442 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations were 0 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concenPations were 0 ppm.
Respirable Particulates (PM2,5)
Respirable particulate concentrations* indoors ranged between 2 pg/m^ to 30 pg/m3 with an average 11 pg/m^ • All of the indoor and outdoor measurements for respirable particulates were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter, and the USEPA recommended concentration of 40 pg/ni3 for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 2 pg/m^ to 10 pg/m^ with an average of 6 pg/m^.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
CONFIDENTIAL, CITY_2IMCI00_003462330 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000259210
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000404522
IAQ measurements collected at the referenced school; BOE program (Apr 22, 2002).
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259244
ATC report of IAQ measurements collected April 25, 2002 for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259471
ATC indoor air quality report for the BOE-ordered measurements at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396719
ATC IAQ measurements collected June 18, 2002 for BOE IAQ maintenance.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404467
IAQ measurements at 100 Trinity Place, performed April 9, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259483
ATC IAQ report documenting measurements collected June 3, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396715
ATC IAQ measurements collected June 17, 2002 as part of BOE monitoring.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396659
IAQ report for measurements collected May 28, 2002 under BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000223584
Report of indoor air quality measurements collected at the High School of Economics and Finance on May 15, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259527
ATC IAQ measurements report for June 19, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396575
ATC IAQ measurements collected May 17, 2002 for BOE program on maintaining IAQ.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404508
ATC IAQ field data for High School of Economics and Finance (M833) project 15-19125-0291.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000223584
Report of indoor air quality measurements collected at the High School of Economics and Finance on May 15, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000223596
Report of indoor air quality measurements collected at the High School of Economics and Finance on June 25, 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404522
IAQ measurements collected at the referenced school; BOE program (Apr 22, 2002).
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396436
May 3, 2002 IAQ measurements for BOE at HSEF (M833).
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000223588
Report of indoor air quality measurements collected at the High School of Economics and Finance on May 23, 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259145
Report of IAQ measurements at 100 Trinity Place for BOE program, March 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000404522
IAQ measurements collected at the referenced school; BOE program (Apr 22, 2002).
Similar indexed content
ATC report of IAQ measurements collected April 25, 2002 for BOE.
Similar indexed content
ATC indoor air quality report for the BOE-ordered measurements at the referenced school.
Similar indexed content
ATC IAQ measurements collected June 18, 2002 for BOE IAQ maintenance.
Similar indexed content
IAQ measurements at 100 Trinity Place, performed April 9, 2002.
Similar indexed content