Indoor air quality memo, high school, Apr 2002

Machine-extracted title · confidence 42%

IAQ measurements collected on Apr 26, 2002; BOE program.

NYC-WTC_000404562–000404565
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan April 29, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833) ATC Project No. 15-19125-0291

Real-Time Environmental Measlrements

ATC collected one hundred (100) sets of real-time environmental measurements consisting of eighty-eight (88) inside the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings were collected between morning to evening. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 68.5°F to 77.0°F. Twenty nine (29) measurements were below and fifty nine (59) measurements were within the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 58.0 "F to 67.4 °F.

Relative Humidity

The relative humidity indoors ranged from 18.8 percent to 27.4 percent. All of the indoor measurements for relative humidity were bellow the ASHRAE recommended range of 30 to 60 ]?ercent for occupant comfort. The outdoor relative humidity ranged from 15.8 to 19.9 percent.

Car^onDipxideConcentratipn

Carbon dioxide concentrations indoors ranged from 444 ppm to 1611 ppm. Two of the indoor measurements for CO2 were high and these readings were detected in Staircase A to 4^ floor indicating CO2 concentration of 1498 ppm with four (4) occupants and Room #410 indicating CO2 concentration of 1611 ppm with twenty six (26) occupants , These measurements were collected at approximately 10:38 AM. Eighty six indoor (86) measurements below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 474 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1174 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

CarbonMonoxideConcentration

Carbon monoxide concentrations indoors ranged from 0 ppm to 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm to 3 ppm.

Respirable Particulates (PM2,5)

Respirable particulate concentrations* indoors ranged between I pg/m^ to 36 pg/m^ with an average 8 pg/m^- All of the indoor and outdoor measurements for respirable particulates were below die NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m3 for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 20 pg/m^ to 65 pg/m^ with an average of 35 pg/m^.

CITY_21MC100_002900398

NYC-WTC_000404564

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000404564Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000396699

ATC IAQ measurements collected June 11, 2002 at the school for BOE IAQ monitoring.

Similar indexed content

NYC-WTC_000259258

ATC report of IAQ measurements collected on April 26, 2002 for BOE.

Similar indexed content

NYC-WTC_000396488

Indoor air quality measurements collected May 9, 2002 for BOE.

Similar indexed content

NYC-WTC_000396687

ATC reports IAQ measurements at High School of Economics and Finance, June 2002, per BOE request.

Similar indexed content

Compare copies and versions →