Indoor air quality report, May 10, 2002

Machine-extracted title · confidence 42%

May 9-10 IAQ measurements at the school, part of BOE program.

NYC-WTC_000384900–000384903
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan May 10, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833)________ ATC Project No. 15-19125-0291 Real-Time Environmental Measurements

ATC collected one hundred (100) sets of real-time environmental measurements consisting of eighty-eight (88) inside the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings were collected between morning to evening. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 62.3 °F to 79.1 °F. Six (6) of the indoor measurements collected were bellow and three (3) measurements were bellow and seventy nine (79) were within the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 57.1 °F to 63.3 °F.

Relative Humidity

The relative humidity indoors ranged from 32.9 percent to 54.3 percent. All of the indoor measurements for relative humidity were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 36.2 to 46.7 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 528 ppm to 1340 ppm. Two (2) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 459 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1159 ppm (background level + 700 ppm). The highest reading (1340 ppm) was measured in stairwell A to 6^^ floor around 11.27 AM. The stairwell was fully occupied at that time. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors ranged from 0 to 1 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 to 3 ppm.

Respirable Particulates (PM2,5)

Respirable particulate concentrations* indoors ranged between 1 pg/m^ to 47 pg/m^ with an average of 9 pg/m^- All of the indoor measurements for respirable particulates were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and one (1) measurement was above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The respirable concentrations outdoors ranged between 19 pg/m^ to 31 pg/m^ with an average of 25 pg/m^-

CITY_21MC100_002882142

NYC-WTC_000384902

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000384902Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000396488

Indoor air quality measurements collected May 9, 2002 for BOE.

Similar indexed content

NYC-WTC_000396699

ATC IAQ measurements collected June 11, 2002 at the school for BOE IAQ monitoring.

Similar indexed content

NYC-WTC_000396687

ATC reports IAQ measurements at High School of Economics and Finance, June 2002, per BOE request.

Similar indexed content

NYC-WTC_000396474

Indoor air quality measurements collected May 8, 2002 for BOE.

Similar indexed content

NYC-WTC_000396683

IAQ measurements collected Jun 5, 2002 for school IAQ maintenance check.

Similar indexed content

Compare copies and versions →