Mr. Bernard P. Orlan April 24, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M8331 ATC Project No. 15-19125-0291

Re AT.-TfME Environmental Mkasurkments

ATC collected seventy three (73) sets of real-time environmental measurements consisting of sixty four (64) inside the school building and nine (9) outdoors. Field data sheets are found in the Attachment. Readings were collected between 2 PM to 5:59 PM. The results are described below.

Tenujerature

Indoor dry bulb temperature measurements ranged from 57.2 °F to 73,4 °F. Sixty one (61) of the measurements were below and four (4) measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 57.2 °F to 62.4 °F . Relative Humidity

The relative humidity indoors ranged from 30.4 percent to 34.6 percent. All of the indoor measurements for relative humidity were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 30.1 to 32.4 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 581 ppm to 972 ppm. All of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) COj concentration was 831 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1531 ppm (background level -t- 700 ppm). Levels above the recommended maximum do not indicate a health risk Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations were 0 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 0 ppm.

Respirable Particulates (PM23)

Respirable particulate concentrations* indoors ranged between 4 pg/m’ to 15 pg/m’ with an average 6 pg/m’ All of the indoor and outdoor measurements for respirable particulates were below the NPAAQS of 65 pg/m’ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter, and the USEPA recommended concentration of 40 pg/m’ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 5 pg/m’to 8 pg/m’ with an average of 6 pg/m’.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

CITY_21MC100_0 02900355

NYC-WTC_000404528

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000404528Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →