Mr. Bernard P. Orlan April 18, 2002 Indoor Air Quality Assessment Page 3 H .S. of Fconnmics and Finance (M833) ATC Project No. 15-19125-0291

Real-time environmental measurements

ATC collected one-hundred (100) sets of real-time environmental measurements consisting of eighty-eight (88) inside the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings began in the morning and concluded in the afternoon. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 81.1 “F to 87.4 °F. All of the indoor measurements for temperature were above the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature ranged from 78.5 to 887.1 °F.

RelatiyeHumidity

The relative humidity indoors ranged from 38.1 percent to 52.1 percent. All of the indoor measurements for relative humidity were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 38.1 to 50.8 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 513 ppm to 1009 ppm. All of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 801 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1501 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations were 3 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 3 ppm.

Respirable Particulates (PM2,s)

Respirable particulate concentrations* indoors ranged between 19 pg/m^ to 40 pg/m^ with an average 31 pg/m^- All of the indoor and outdoor measurements for respirable particulates were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 48 pg/m^ to 101 pg/m^ with an average of 71 pg/m^.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TyOCCpncentrgtign

CITY_21MC100_002900295

NYC-WTC_000404506

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000404506Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000396645

ATC IAQ measurements collected May 24, 2002 for IAQ assessment.

Similar indexed content

NYC-WTC_000396723

ATC IAQ measurements collected June 19, 2002 under BOE IAQ program.

Similar indexed content

NYC-WTC_000385115

ATC IAQ measurements collected June 18, 2002 for BOE at the High School of Economics and Finance.

Similar indexed content

Compare copies and versions →