Indoor Air Quality Assessment Page 4
P. S. 89M ATC Project No. 15-19125-0297
asthmatic people and children. The outdoor respirable particulate concentration averaged 31
pg/m3 (A.M.) and 11 pg/m^ (P.M.).
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concentration..
TVOCs were not detected (0.0 ppm) anywhere inside or outside the building.
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• The school was partially occupied (I.S. 89) at the time of the assessment;
• No smoke odor was detected in the building.
nNDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of PM2.5, CO2, CO and TVOCs were within applicable guidelines.
2. Five (5) temperature measurements were below and two (2) were above the ASHRAE-
recommended range.
3, All indoor measurements of relative humidity were below the ASHRAE recommended range
of 30 to 60 percent for occupant comfort.