NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan February 13, 2002
Indoor Air Quality Assessment Page 4
P. S. 89M ATC Project No. 15-19125-0297
asthmatic people and children. The outdoor respirable particulate concentration averaged 15
pg/m3 (A.M.) and 15 pg/m^ (P.M.).
* The measurements made during this assessment were instantaneous readings, the NP/vAQS is
a 24-hour average.
TVOC Concentration..
TVOCs were not detected (0.0 ppm) anywhere inside or outside the building.
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• The school was partially occupied (I.S. 89) at the time of the assessment;
• No smoke odor was detected in the building.
FINDINGS
Based on the real-time measurements, the following findings are presented;
1. Concentrations of PM2.5, CO2, CO and TVOCs were within applicable guidelines.
2. Seventeen (17) temperature measurements were below the ASHRAE-recommended range.
3. All indoor measurements of relative humidity were below the ASHRAE recommended range
of 30 to 60 percent for occupant comfort.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
261 or 212.
Sincerely,
A TC ASSOCIA TES INC.
/ / Yiannis Efstatniou James R. Cohn, CIH, CSP
Project Manager Regional Manager
Industrial Hygiene Division
Attachment
CITY_21MC100_003109780
NYC-WTC_000274625
OCR can misread numbers and units. Confirm readings against the page image before using them.