Mr. Bernard P. Orlan January 17, 2002 Indoor Air Quality Measurements Page 4 Stuvvesant Hieh School (M477) ArCPrpiectNpJ^-1912S:0246

was 5-21 pg/m^ with an average of approximately 9 pg/m^. The PM2.5 concentration range for the other rooms was 4-23 pg/m^ with an average of approximately 8 pg/m^. The average PM2.5 concentration for the entire school building was approximately 8 pg/m^. In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740.

The PM2.5 concentration range for these rooms was 5 - 15 pg/m^ with an average of approximately 10 pg/m^.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentration

TVOCs were not detected” anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building; • The portable HEPA air purifiers in Rooms 333, 638 and 740 were turned off;

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of CO and TVOCs were within applicable standards and guidelines.

2. One (1) CO2 measurement was above the .range recommended by ASHRAE 62-1999. All others were below the recommended maximum concentration.

3. One hundred and twenty-five (125) indoor measurements of relative humidity were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort.

4. Three (3) temperature measurement were below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions).

5. None of the respirable particulate measurements were above the NPAAQS of 65 pg/m^ 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter.

CITY_21MC100_002897816

NYC-WTC_000401839

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000401839Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000402182

March 12, 2002 IAQ measurements report for Stuyvesant High School.

Similar indexed content

Compare copies and versions →