NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan March 13, 2002
Indoor Air Quality Measurements Page 4
Stuvvesant Hieh School (M477') ATCProiectNo. 15-19125-0246
In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency
Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM?.5
concentration range for these rooms was 7-21 pg/m^ with an average of approximately 14
Hg/ni3.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concentration
TVOCs inside the building wereO.O ppm to 0.1 ppm The outdoor TVOC concentrations were 0.1
ppm to 0.2 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building; .
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Measurements of temperature and concentrations of respirable particulates, CO ,CO2, and
TVOCs, were within applicable standards and guidelines.
2. Sixty-five (65) measurements of relative humidity were below the ASHRAE recommended
range of 30 to 60 percent for occupant comfort.
It is our pleasure to provide these indoor air quality, services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
211 or 212.
Sincerely,
A TC ASSOCIA TES INC.
Reviewed by:
Yiannis Efstathiou James R. Cohn, CIH, CSP
Project Manager Regional Manager
Industrial Hygiene Division
Attachment