ATC respirable particulate IAQ assessment report for Stuyvesant High School (M477), Apr 2002.

NYC-WTC_000401078–000401080
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan April 10, 2002 Respirable Particulate Assessment Page 3 Stuvvesant High School (M477') ATC Project No. 15-19125-0246

The Dust Trak® detects volatile aerosol particles that are not recovered by the gravimetric method. The PM, 5 concentrations measured by the Dust Trak® were generally close to those measured with the MEM® in this set of results. On March 11-12 and March 19-20, the Dust Trak® measurements were approximately half the gravimetric results. These are the exceptions to the pattern that has been so far observed. The,Dust Trak® results from the other four days are greater than the MEM® results by <1% to 20%.

The calibration factor of the Dust Trak® was electronically reset from 1.00 to 0.34 and the reset instrument was put in place beginning with the February 25-26 sampling period. The adjustment was made, based on previous side-by-side sampling results, to see if the Dust Trak® data would more closely approximate the gravimetric results. This was reset again to 0.5 on March 4, 2002. The results obtained show that this may be a reasonable conversion factor although there still will be differences between the gravimetric method and the Dust Trak®.

Results by both methods on all eight days were below the EPA NPAAQS of 65 ug/m’ and the EPA recommended level of 40 ug/m\ -3

CONCLUSION

Side-by-side sampling conducted to date does not indicate a predictable conversion factor for results from these two instruments. The Dust Trak® can provide instantaneous readings that may be used to demonstrate trends in PM. , concentrations but it should not be used to determine compliance with EPA standards. The results are subject to misinterpretation.

Sample results obtained by both instruments were below both the EPA NPAAQS for PM2 5 of 65 ug/m^ (24-hour average) and the EPA recommended level of 40 ug/m\

It is our pleasure to provide these indoor air consultative services to the New York City Board of Education. If you have any questions about this report, please call (212) 353- 8280, extension 212.

Sincerely, ATC ASSOCL4TES INC.

James R. Cohn, CIH, CSP Regional Manager, Industrial Hygiene Division

Attachments

CITY_21MC100_002896804

NYC-WTC_000401080

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000401080Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000308767

ATC report on six-date respirable particulate monitoring at the school building.

Similar indexed content

Compare copies and versions →