IAQ report, 90 Trinity Place, June 2002

Machine-extracted title · confidence 41%

June 6, 2002 IAQ measurement report for the referenced school.

NYC-WTC_000399520–000399523
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan June 06, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M894) ATCProiectNo. 15-19125-0290

Real-Time Environmental Measurements

ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings were collected in the morning and evening. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 73.4 to 82.1 °F. Forty-six (46) of the indoor measurements for temperature were above and Eighty-two (82) measurements were within the range of 73 to79 °F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature ranged from 76.4 to 88.3 °F.

RelatrveHumidify

The relative humidity indoors ranged from 42.6 percent to 56.9 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 58.9 to 68.2 percent.

C^bon^oxideConc^tration

Carbon dioxide concentrations indoors ranged from 649 ppm to 1423 ppm. All of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 627 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1327 ppm (background level -1- 700 ppm). The highest reading (1423 ppm) was recorded in 14th floor hallway at about 4:00 PM.Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxi^ Concentration

Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm to 3 ppm.

Respirable Particulates (PM2_3)

Respirable particulate concentrations* indoors ranged between 4 pg/m^ to 21 pg/m^ with an average 10 pg/m^- None of the indoor measurements for PM2 5 were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m3 for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 64 pg/m^ to 174 pg/m^ with an average of 101 pg/m^.

CITY_21MC100_002895877

NYC-WTC_000399522

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000399522Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000291988

ATC IAQ measurements collected June 11, 2002 for the referenced BOE school.

Similar indexed content

Compare copies and versions →