NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan May 22, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M894) ATC^oiectNo. 15-19125-0290

Real-Time Environmental Measurements

ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings were collected in the morning and evening. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 71.0 °F to 80.1 °F. Thirteen (13) of the indoor measurements for temperature were below and one (1) was above the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature ranged from 65.7 to 69.1°F,

Relative Humidity

The relative humidity indoors ranged from 24.4 percent to 48.3 percent. Seventy-nine (79) of the indoor measurements for relative humidity were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 21.9 to 27.1 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 549 ppm to 1864 ppm. Twenty-two (22) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 571 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1271 ppm (background level + 700 ppm). Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

CarbonMono^e Concentration

Carbon monoxide concentrations indoors were 2 ppm for all collected readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were also 2 ppm for all readings.

Respirable Particulates (PM2jj

Respirable particulate concentrations* indoors ranged between 6 pg/m^ to 16 pg/m^ with an average 11 pg/m^- None of the indoor measurements for PM2,5 were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA recommended concentration of 40 pg/m3 for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 33 pg/m^ to 41 pg/m^ with an average of 36 pg/m^.

CITY_21MC100_002895687

NYC-WTC_000399426

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000399426Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000399222

Indoor air quality measurements at the High School for Leadership & [name]; May 2002.

Similar indexed content

NYC-WTC_000399366

May 15, 2002 IAQ measurements report for BOE.

Similar indexed content

NYC-WTC_000211859

Letter and report from ATC Associates detailing indoor air quality measurements collected at the school on March 25, 2002, to evaluate possible contamination.

Similar indexed content

Compare copies and versions →