July 26, 2002
Mr. Bernard P. Orlan
Director, Environmental Health and Safety
New York City Board of Education
28-11 Queens Plaza North
Long Island City, NY 11101
Re: Air Sampling for Metals
High School for Leadership & Public Service (M894)
ATC Project No. 15-19125-0290
Dear Mr. Orlan:
ATC Associates, Inc. (ATC) is pleased to provide this letter report of air sampling for metals in
airborne dust on June 14 and 21, 2002, at the referenced school. The New York City Board of
Education (BOE) requested this sampling to determine if acceptable indoor air quality is being
maintained.
Scope of Work
ATC collected four (4) samples for metals at specified locations. Samples were collected for a
minimum of ten (10) hours using 37 mm mixed cellulose ester filter connected to battery-
powered sampling pumps at a flow rate of 2 liters per minute. Pumps were calibrated before and
after each sampling period. Two (2) samples were collected inside the building and two (2) were
collected outdoors. Two blanks were submitted per day. The additional blank was included to
confirm the levels of any trace contaminants in the filters. The samples were sent to PSC
Analytical Services, Inc., an American Industrial Hygiene Association-accredited laboratory in
Reading, PA. Analysis was performed by NIOSH Method 7300M. Each sample was analyzed for
a panel of twelve (12) metals. The metals were aluminum (Al), cadmium (Cd), chromium (Cr),
cobalt (Co), copper (Cu), iron (Fe), lead (Pb), magnesium (Mg), manganese (Mn), molybdenum
(Mo), nickel (Ni) and zinc (Zn). Copies of the analytical laboratory reports are attached.
The sampling locations were the Main Entrance Lobby, 5* floor elevator lobby, 10* floor
elevator lobby and the Roof.
Tenzin Namgyal and Wagdi Abdelshahid, Industrial Hygienists from ATC’s New York City
office, conducted the sampling consistent with accepted industrial hygiene practices. The results
represent the conditions on the days the samples were collected.
The established regulatory values for metals are intended for industrial workplace exposures and
are not generally applicable to office/school settings. There are no standards for these metals in
indoor air in non-industrial situations.